Current transformer failure caused by electric field associated to circuit breaker and pollution in 500 kV substations
Introduction
In the last years, the consumption of electricity is continuously growing, in the power system to consumers is carried out using high voltage power lines and substations, in Perú the transmission systems has been built across the country in a voltage of 500 kV [1], in order to further utilize the power lines for industrial and mining needed, however some particulars problems has been detected, as pollution caused by sea winds [2], among others. This type of voltage level in the coast doesn't have lightning problems [3], but the electric and magnetic problems should be considered for invisible degradation, even more, the international standards don't consider some characteristics in the design, it is a real failure mode for the maintenance [4].
The modern substations for high voltage have required special considerations for the electrical phenomenon in this voltage level, the recovery transitory voltage in the circuit breaker [1, 23], the overvoltage for the series capacitors in the large overhead lines, power transformers with degradation [27, 28], rupture of the cables and guard wires [30] and FACT failures with stability power system problems [31].
In 500 kV substations, physical layout drawings have written with the insulation co-ordination standard [5], besides due to the fact that the power frequency is 60 Hz, time harmonic electric and magnetic fields are considered quasistatic [6], therefore, electric field is calculated separately.
Different approaches for electric field on Overhead lines (OHL) and substations has been demonstrated with simple geometries in a 2D models, without a correct approach [7]. Due to this problem, the 3D modeling with complex geometries has been considered with Charge simulation methods (CSM) for electric field in substations, other as hybrid CSM has been worked too [8, 9]. In 2018, a computation of electric fields inside substation has been performed based on integral equations approach, it shape functions of change densities over the elements of HV facility [10]. However the electric and magnetic field haven't calculated for an interaction in the same phase and with pollutions components. Finally, others internationals standards just recommend a human exposure to electromagnetic field for 0 to 3 kHz, for an electromagnetic and human interaction in the substations and OHL [11]. Generally accepted guidelines have been established for safe public and occupational exposure to power-frequency electromagnetic field.
The reference levels for general public exposure to 60 Hz, electric and magnetic field are, according to International Commission on Non-Ionizing Radiation Protection (ICNIRP) guidelines, are the followings [14]:
- -
Electric field strength, E < 5 kV/m
- -
Magnetic field strength, H < 80 A/m
- -
Magnetic flux density, B < 100 μT
And for occupations exposure are the followings:
- -
Electric field strength, E < 10 kV/m
- -
Magnetic field strength, H < 400 A/m
- -
Magnetic flux density, B < 500 μT
The problem solved in this research, is related to the development of a failure assessment using finite elements for high voltage current transformers and circuit breaker, two important assets to ensure the normal operation of power system, of which the reliability is largely dependent on the normal operation of the correct operation systems [12], to find various approach. The system can be applicable in the fault warning, maintenance of current transformer, to provide bases for design and physical layout plan in new 500 kV substations [21]. The purpose of this research is to explain how an electric field (EF) with pollution and humidity conditions affect the current transformer caused by high influence of EF, finally, it has been analyzed by a root caused analysis (RCA) in 3 current transformers explosion, it has occurred in Peru, in the same substation for the same one and half scheme at 500 kV substation.
Section 2 considers the internal assessment for 500 kV substations layout, calculations methods; in Section 3, failure analysis has been done with an implementation of adaptive approximation, it describes the input data, electric potentials, gradient potentials in the equipment and oil. Section 4 has considered the root cause analysis for this equipment explosion, in the next Section 5, the numerical benchmarking is done, and finally, the last section is the conclusion for the knowledge management in energy companies, for the internationals standards upgraded and future substations design.
Section snippets
500 kV substations layout
Substations are points in the power network where transmission lines and distribution feeders are connected though circuit breakers or switches via bus bars and transformer. This allows for the control of power flows in the network and general switching operations for maintenance purposes. In an ideal situation all circuits and substation equipment would be duplicated such that following a fault or during maintenance a connection remains available. This would involve high cost, method have
Input data
The substation scheme in 500 kV is a 1½ configuration is indicated in Fig. 4.
In Fig. 4, the current transformer is in the number 1, the connectors are in the number 2, the circuit breaker is indicated in Fig. 3 and finally the connectors are in the number 4. The information for input data model is the indicated in Fig. 5, and Table 3.
The system values are the followings:
- -
Voltage system is 525 kV, the design value of the transformer insulation is taken for the simulation. The service criteria is
Root cause analysis
About the root cause analysis (RCA) for the current transformer explosion is indicated in Fig. 20, it should considered five hypothesis in the analysis as follow:
- -
Internal damage for overvoltage caused by the grid.
- -
Maintenance inadequate.
- -
High degree of effluvia due to ionization of the air, caused by insulation contamination, air humidity and inadequate creepage distance in the insulators.
- -
Equipment assembly inadequate.
- -
Design inadequate or quality control inadequate in the factory.
In the first
Numerical benchmarking against measurement
In order to demonstrate advantages of developed methods for the computation of power frequency electric fields and electromagnetic field in substations, 500 kV substations design are selected for analysis electric field, electromagnetic field and benchmarking against measurements.
The International Commission on Non-Ionizing Radiation Protection (ICNIRP) provided the guidelines [14, 18], occupational exposure limit for power frequency electric field determined by legislative in Croatia is Emax
Conclusions
In this research, different aspects related to electric field interaction between current transformers and circuit breaker in 500 kV substations have been investigated. A failure in the current transformer has been modeled with finite element Method, besides a RCA has been realized.
The main aspects are the followings.
- -
The electrical potential extends through the air from the current transformer to the circuit breaker, it has been behaving differently between the case where the transformer is at
Acknowledgment
Recognition of the company Red de Energia del Peru, FreePort-McMoRan Inc., ENEL GREEN POWER and Pontificia Universidad Catolica del Perú (PUCP), Doctoral Engineering Program for the support and development of this research.
References (31)
- et al.
Computation of Electric Field inside Substation with Boundary Element Methods and Adaptive Cross Approximation. Engineering Analysis with Boundary Elements
(2018) - et al.
Transmission and Distribution Electrical Engineering
(2012) - et al.
Finite element analysis of substation composite insulators
Compos. Sci. Technol.
(1995) - et al.
Life estimation of shunt power reactors considering a failure core heating by floating potentials
Eng. Fail. Anal.
(2018) - et al.
Circuit breakers 500 kV degradation in substation reactors caused by inductive current
Eng. Fail. Anal.
(2018) - et al.
The need of creating a new nominal creepage distance in accordance with heaviest pollution 500 kV overhead line insulators
Eng. Fail. Anal.
(2018) - et al.
Electrical assessment by lightning phenomenon in power lines of double circuit
IEEE Lat. Am. Trans.
(2016) - et al.
Electric field and electromagnetic environment analyses of a 500 kV composite cross arm
IEC 60071-1 Insulation Co-Ordination – Part 1
(2011)- et al.
Electromagnetic Fields, Waves, and Numerical Methods
(2000)
Comparison of 2D algorithms for the computation of power line electric and magnetic fields
Eur. Trans. Electr. Power
Generalized charge simulation method for the calculation of the electric field in high voltage substations
Electr. Eng.
Numerical modeling of the electric field in HV substations
IEE Proc. Sci. Meas. Technol.
C95.6 IEEE Standard for Safety Levels with Respect to Human Exposure to Electromagnetic Fields, 0–3 kHz
Research on expert diagnosis system for mechanical fault of high voltage circuit breaker based on fuzzy matrix and neural network technology
Cited by (28)
Study on a 110 kV combined prefabricated joint fault caused by premature failure of grounding grid
2022, Engineering Failure AnalysisFailure analysis and dispatch optimization using phasor measurement units
2021, Engineering Failure AnalysisStretched grid finite difference method for computation of electric field in composite insulators with defects
2021, Electric Power Systems ResearchRoot cause analysis improved with machine learning for failure analysis in power transformers
2020, Engineering Failure AnalysisRoot cause analysis methodology for circuit breaker associated to GIS
2020, Engineering Failure AnalysisNew methodology for design and failure analysis of underground transmission lines
2020, Engineering Failure AnalysisCitation Excerpt :Transmission lines tend to provoke more massive objection, because of significant visual impact in connection with very limited benefits to those affected [11]. “The emphasis on environmental assessment and planning is moving away from environmental control to integrated resource planning taking account of environmental impacts” [10]. By the way, the underground conductors for high voltage application have the followings design and factory acceptance test: