Influence of reduced VAV flow settings on indoor thermal comfort in an office space

  • Research Article
  • Indoor/Outdoor Airflow and Air Quality
  • Published:
Building Simulation Aims and scope Submit manuscript

Abstract

The air temperature distribution in a space with reduced diffuser flow rates and heat loads was studied using simulation. Computational fluid dynamics (CFD) was used to analyze the room air distribution from a side wall diffuser at the design flow rate, and the results were validated with experimental data. CFD was used to predict occupant discomfort under a range of reduced diffuser flow rates. It was found for diffuser flow rates above 30% of the design flow rate that the temperature influence from the jet was minimal. At these flow rates, there was nearly a uniform temperature distribution in the occupied zone. The predicted maximum value of percentage of dissatisfied occupants within the space began to increase for diffuser flow rates below 30% of the design flow rate. The percent dissatisfaction at 1 m room height was greater than 25% for the lowest diffuser flow rate tested (15% of the design flow rate) directly under the diffuser, which was the highest of the test cases, but was 5% or less throughout more than 90% of the room. In contrast, at the higher flow rates, the percent dissatisfied index was 5% or less in only 60%–80% of the room due to increased velocity. Evidence of dumping was already found at the traditional minimum flow rate setting of 30% of design, and so there would be little harm in reducing the minimum flow rate further. Reducing the flow rate below 30% of design just moved the location of the dumping closer to the diffuser. For very low diffuser flow rates (below 30% of the design flow rate), it is recommended that desks be placed away from the supply diffuser to avoid discomfort. Overall, the simulation results indicate that uniform temperatures are maintained in the room at flow rates as low as 15% of design except immediately under the diffuser. This suggests that the VAV minimum flow rates can be set below 30% of design flow as long as the diffuser is at least 1 m from an occupant’s position.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Institutional subscriptions

Similar content being viewed by others

References

  • ANSYS (2013). ANSYS Mechanical User’s Guide.

    Google Scholar 

  • Arens E, Zhang H, Hoyt T, Kaam S, Goins J, Bauman F, Zhai Y, Webster T, West B, Paliaga G, Stein J, Seidl R, Tully B, Rimmer J, Toftum J (2012). Thermal and air quality acceptability in buildings that reduce energy by reducing minimum airflow from overhead diffusers. ASHRAE RP-1515.

    Google Scholar 

  • Arens E, Xu T, Miura K, Hui Z, Fountain M, Bauman F (1998). A study of occupant cooling by personally controlled air movement. Energy and Buildings, 27: 45–59.

    Article  Google Scholar 

  • ASHRAE (2013). Thermal environmental conditions for human occupancy. ANSI/ASHRAE Standard 55-2013.

    Google Scholar 

  • Cândido C, de Dear RJ, Lamberts R, Bittencourt L (2010). Air movement acceptability limits and thermal comfort in Brazil’s hot humid climate zone. Building and Environment, 45: 222–229.

    Article  Google Scholar 

  • Carlucci S, Pagliano L (2012). A review of indices for the long-term evaluation of the general thermal comfort conditions in buildings. Energy and Buildings, 53: 194–205.

    Article  Google Scholar 

  • Charles KE (2003). Fanger’s thermal comfort and draught models. National Research Council of Canada, IRC Research Report RR-162.

    Google Scholar 

  • Chen Q (1995). Comparison of different k–e models for indoor airflow computations. Numerical Heat Transfer, Part B: Fundamentals, 28: 353–369.

    Article  Google Scholar 

  • Chen Q, Moser A (1991). Simulation of a multiple-nozzle diffuser. In: Proceedings of 12th AIVC Conference, Ottawa, Canada, pp. 1–14.

    Google Scholar 

  • Cheng Y, Niu J, Gao N (2012). Thermal comfort models: A review and numerical investigation. Building and Environment, 47: 13–22.

    Article  Google Scholar 

  • Cheong KWD, Djunaedy E, Chua YL, Tham KW, Sekhar SC, Wong NH, Ullah MB (2003). Thermal comfort study of an air-conditioned lecture theatre in the tropics. Building and Environment, 38: 63–73.

    Article  Google Scholar 

  • De Dear RJ, Akimoto T, Arens E, Brager G, Candido C, Cheong KWD, Li B, Nishihara N, Sekhar SC, Tanabe S, Toftum J, Zhang H, Zhu Y (2013). Progress in thermal comfort research over the last twenty years. Indoor Air, 23: 442–461.

    Article  Google Scholar 

  • Djongyang N, Tchinda R, Njomo D (2010). Thermal comfort: A review paper. Renewable and Sustainable Energy Reviews, 14: 2626–2640.

    Article  Google Scholar 

  • Ewert M, Renz U, Vogl N, Zeller M (1991). Definition of the flow parameters at the room inlet devices-measurements and calculations. In: Proceedings of 12th AIVC Conference, Ottawa, Canada, pp. 231–237.

    Google Scholar 

  • Fanger P, Melikov A, Hanzawa H, Ring J (1988). Air turbulence and sensation of draft. Energy and Buildings, 12: 21–39.

    Article  Google Scholar 

  • Fanger P, Christensen N (1986). Perception of draught in ventilated spaces. Ergonomics, 29: 215–235.

    Article  Google Scholar 

  • Fountain M, Bauman F, Arens E, Miura K, de Dear R (1994). Locally controlled air movement preferred in warm isothermal environments. ASHRAE Transactions, 100(2): 937–952.

    Google Scholar 

  • Gosman A, Nielsen P, Restivo A, Whitelaw J (1980). The flow properties of rooms with small ventilation openings. Journal of Fluids Engineering, 102: 316–323.

    Article  Google Scholar 

  • Heikkinen J (1991a). Modeling of a supply air terminal for room airflow simulation. In: Proceedings of 12th AIVC Conference, Ottawa, Canada, pp. 213–230.

    Google Scholar 

  • Heikkinen J (1991b). Measurements of test cases B2, B3, E2, E3 (isothermal and summer cooling cases). IEA Annex 20 Research item 1.16 and 1.17.

    Google Scholar 

  • Huo Y, Zhang J, Shaw C, Haghighat F (1996). A new method to describe boundary conditions in CFD simulation. In: Proceedings of International Conference on Air Distribution in Rooms (ROOMVENT), Yokohama, Japan, pp. 233–240.

    Google Scholar 

  • Kajiya R, Hiruta K, Sakai K, Ono H, Sudo T (2011). Thermal environment prediction using CFD with a virtual mannequin model and experiment with subject in a floor heating room. In: Proceedings of 12th International IBPSA Building Simulation Conference, Sydney, Australia, pp. 1670–1677.

    Google Scholar 

  • Kubo H, Isoda N, Enomoto-Koshimizu H (1997). Cooling effects of preferred air velocity in muggy conditions. Building and Environment, 32: 211–218.

    Article  Google Scholar 

  • Kwong QJ, Adam NM, Sahari BB (2014). Thermal comfort assessment and potential for energy efficiency enhancement in modern tropical buildings: A review. Energy and Buildings, 68: 547–557.

    Article  Google Scholar 

  • Lemaire AD, Chen Q, Ewert M, Heikkinen J, Inard C, Moser A, Nielsen PV, Whittle G (1993). Room air and contaminant flow, evaluation of computational methods. Subtask-1 Summary Report.

    Google Scholar 

  • Luo S, Heikkinen J, Roux B (2004). Simulation of airflow in the IEA annex 20 test room—Validation of a simplified model for the nozzle diffuser in isothermal test cases. Building and Environment, 39: 1403–1415.

    Article  Google Scholar 

  • Mendell MJ, Mirer AG (2009). Indoor thermal factors and symptoms in office workers: Findings from the US EPA BASE study. Indoor Air, 19: 291–302.

    Article  Google Scholar 

  • Nielsen PV (1992). The description of supply openings in numerical models for room air distribution. ASHRAE Transactions, 98(1): 963–971.

    Article  Google Scholar 

  • Nielsen PV (1989). Representation of boundary conditions at supply openings. IEA Annex 20 Research Item No. 1.11.

    Google Scholar 

  • Noh K, Jang J, Oh M (2007). Thermal comfort and indoor air quality in the lecture room with 4-way cassette air-conditioner and mixing ventilation system. Building and Environment, 42: 689–698.

    Article  Google Scholar 

  • Riachi Y, Clodic D (2014). A numerical model for simulating thermal comfort prediction in public transportation buses. International Journal of Environmental Protection and Policy, 2: 1–8.

    Article  Google Scholar 

  • Rupp RF, Vásquez NG, Lamberts R (2015). A review of human thermal comfort in the built environment. Energy and Buildings, 105: 178–205.

    Article  Google Scholar 

  • Simone A, Olesen BW, Stoops JL, Watkins AW (2013). Thermal comfort in commercial kitchens (RP-1469): Procedure and physical measurements (part 1). HVAC&R Research, 19: 1001–1015.

    Article  Google Scholar 

  • Skovgaard M, Nielsen P (1991). Modeling complex inlet geometries in CFD applied to airflow in ventilated rooms. In: Proceedings of 12th AIVC Conference, Ottawa, Canada, pp. 183–200.

    Google Scholar 

  • Srebric J, Chen Q (2002). Simplified numerical models for complex air supply diffusers. HVAC&R Research, 8: 277–294.

    Article  Google Scholar 

  • Srebric J, Chen Q (2001). A method of test to obtain diffuser data for CFD modeling of room airflow (RP-1009). ASHRAE Transactions, 107(2): 108–116.

    Google Scholar 

  • Srebric J (2000). Simplified methodology for indoor environment design. PhD Dissertation, Massachusetts Institute of Technology, USA.

    Google Scholar 

  • Stamou AI, Katsiris I, Schaelin A (2008). Evaluation of thermal comfort in Galatsi arena of the Olympics “Athens 2004” using a CFD model. Applied Thermal Engineering, 28: 1206–1215.

    Article  Google Scholar 

  • Svidt K (1994). Investigation of inlet boundary conditions for numerical prediction of airflow in livestock buildings. Aalborg University, Indoor Environmental Technology, No. 38. Vol. R9407.

    Google Scholar 

  • Taleghani M, Tenpierik M, Kurvers S, van den Dobbelsteen A (2013). A review into thermal comfort in buildings. Renewable and Sustainable Energy Reviews, 26: 201–215.

    Article  Google Scholar 

  • Yang L, Yan H, Lam JC (2014). Thermal comfort and building energy consumption implications—A review. Applied Energy, 115: 164–173.

    Article  Google Scholar 

  • Zhang H, Arens E, Fard SA, Huizenga C, Paliaga G, Brager G, Zagreus L (2007). Air movement preferences observed in office buildings. International Journal of Biometeorology, 51: 349–360.

    Article  Google Scholar 

Download references

Author information

Authors and Affiliations

Authors

Corresponding author

Correspondence to Mitchell T. Paulus.

Rights and permissions

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Gangisetti, K., Claridge, D.E., Srebric, J. et al. Influence of reduced VAV flow settings on indoor thermal comfort in an office space. Build. Simul. 9, 101–111 (2016). https://doi.org/10.1007/s12273-015-0254-3

Download citation

  • Received:

  • Revised:

  • Accepted:

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s12273-015-0254-3

Keywords

Navigation