A review of condition monitoring techniques and diagnostic tests for lifetime estimation of power transformers

  • Original Paper
  • Published:
Electrical Engineering Aims and scope Submit manuscript

Abstract

Power transformers are a key component of electrical networks, and they are both expensive and difficult to upgrade in a live network. Many utilities monitor the condition of the components that make up a power transformer and use this information to minimize the outage and extend the service life. Routine and diagnostic tests are currently used for condition monitoring and appraising the ageing and defects of the core, windings, bushings and tap changers of power transformers. To accurately assess the remaining life and failure probability, methods have been developed to correlate results from different routine and diagnostic tests. This paper reviews established tests such as dissolved gas analysis, oil characteristic tests, dielectric response, frequency response analysis, partial discharge, infrared thermograph test, turns ratio, power factor, transformer contact resistance, and insulation resistance measurements. It also considers the methods widely used for health index, lifetime estimation, and probability of failure. The authors also highlight the strengths and limitations of currently available methods. This paper summarizes a wide range of techniques drawn from industry and academic sources and contrasts them in a unified frame work.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Fig. 6
Fig. 7
Fig. 8
Fig. 9
Fig. 10
Fig. 11
Fig. 12
Fig. 13
Fig. 14

Similar content being viewed by others

References

  1. Jahromi A et al (2009) An approach to power transformer asset management using health index. IEEE Electr Insul Mag 2(25):20–34

    Article  Google Scholar 

  2. Saha TK, Purkait P (2004) Investigation of an expert system for the condition assessment of transformer insulation based on dielectric response measurements. IEEE Trans Power Deliv 19(3):1127–1134

    Article  Google Scholar 

  3. Gockenbach E, Borsi H (2008) Condition monitoring and diagnosis of power transformers. In: International conference on condition monitoring and diagnosis, 2008. CMD 2008. IEEE

  4. Zhang X, Gockenbach E (2008) Asset-management of transformers based on condition monitoring and standard diagnosis [feature article]. IEEE Electr Insul Mag 24(4):26–40

    Article  Google Scholar 

  5. Florian Predl MR (2015) Case studies on tap changer diagonostics using dynamic winding resistance measurement. Omicron Seminar, Perth, WA

  6. Ashkezari AD et al (2011) Evaluating the accuracy of different DGA techniques for improving the transformer oil quality interpretation. In: Universities power engineering conference (AUPEC) 2011 21st Australasian

  7. Arakelian V (2002) Effective diagnostics for oil-filled equipment. IEEE Electr Insul Mag 6(18):26–38

    Article  Google Scholar 

  8. Guidelines for life management techniques for power transformers, CIGRE. Technical Brochure 227 (2003)

  9. IEEE guide for the interpretation of gases generated in oil-immersed transformers. IEEE Std C57.104 (2008)

  10. Tenbohlen S, Figel F (2000) On-line condition monitoring of power transformers. In: Power engineering society winter meeting, 2000. IEEE

  11. IEEE guide for the interpretation of gases generated in oil-immersed transformer. IEEE Std C57.104 (1991)

  12. Akbari A et al (2008) A software implementation of the Duval Triangle method. In: Conference record of the 2008 IEEE international symposium on electrical insulation, 2008. ISEI 2008

  13. IEC International Standard for Mineral oil-impregnated electrical equipment in service—guide to the interpretation of dissolved and free gas analysis. International Electrotechnical Commission, IEC60599:2.1 (2007)

  14. Hettiwatte SN, Fonseka HA (2012) Analysis and interpretation of dissolved gases in transformer oil: a case study. In: 2012 International conference on condition monitoring and diagnosis (CMD)

  15. Islam MM, Lee G, Hettiwatte SN (2016) A nearest neighbour clustering approach for incipient fault diagnosis of power transformers. Electr Eng. doi:10.1007/s00202-016-0481-3

  16. Abu-Elanien AEB, Salama MMA, Ibrahim M (2011) Determination of transformer health condition using artificial neural networks. In: 2011 International symposium on innovations in intelligent systems and applications (INISTA)

  17. Pal M, Foody GM (2010) Feature selection for classification of hyperspectral data by SVM. IEEE Trans Geosci Remote Sens 48(5):2297–2307

    Article  Google Scholar 

  18. Abu-Elanien AEB, Salama MMA, Ibrahim M (2012) Calculation of a health index for oil-immersed transformers rated under 69 kV using fuzzy logic. IEEE Trans Power Deliv 27(4):2029–2036

    Article  Google Scholar 

  19. Bakar NA, Abu-Siada A (2016) Fuzzy logic approach for transformer remnant life prediction and asset management decision. IEEE Trans Dielectr Electr Insul 23(5):3199–3208

    Article  Google Scholar 

  20. Islam MM, Lee G, Hettiwatte SN (2016) Incipient fault diagnosis in power transformers by clustering and adapted KNN. In: 2016 Australasian Universities power engineering conference (AUPEC)

  21. IEC, Measurement of relative permittivity, dielectric dissipation factor and d.c. resistivity of insulating liquids, IEC 60247 Ed. 2.0 (2004)

  22. Ashkezari AD et al (2013) Application of fuzzy support vector machine for determining the health index of the insulation system of in-service power transformers. IEEE Trans Dielectr Electr Insul 20(3):965–973

    Article  Google Scholar 

  23. IEC, Insulating liquids—Determination of acidity—Part 1: automatic potentiometric titration, IEC 62021-1 (2003)

  24. Rouse TO (1998) Mineral insulating oil in transformers. IEEE Electr Insul Mag 14(3):6–16

    Article  Google Scholar 

  25. Baka NA et al (2015) A new technique to measure interfacial tension of transformer oil using UV-Vis spectroscopy. IEEE Trans Dielectr Electr Insul 22(2):1275–1282

    Article  Google Scholar 

  26. Li Y et al (2016) Molecular dynamics simulation of temperature impact on the viscosity of transformer oil-based nanofluids. In: 2016 International conference on condition monitoring and diagnosis (CMD)

  27. IEEE guide for the reclamation of insulating oil and criteria for its use, IEEE Std. 637 (2007)

  28. Utami N et al (2009) Evaluation condition of transformer based on infrared thermography results. In: IEEE 9th international conference on the properties and applications of dielectric materials, 2009. ICPADM 2009. IEEE

  29. Saha T, Purkait P (2008) Understanding the impacts of moisture and thermal ageing on transformer’s insulation by dielectric response and molecular weight measurements. IEEE Trans Dielectr Electr Insul 15(2):568–582

    Article  Google Scholar 

  30. IEEE guide for loading mineral–oil-immersed transformers, IEEE Std. C57.91 (2002)

  31. Wang M, Vandermaar A, Srivastava KD (2002) Review of condition assessment of power transformers in service. IEEE Electr Insul Mag 18(6):12–25

    Article  Google Scholar 

  32. IEEE standard test code for liquid-immersed distribution, power, and regulating transformers, IEEE Std. C57.12.90 (2006)

  33. Malik H, Azeem A, Jarial R (2012) Application research based on modern-technology for transformer health index estimation. In: 2012 9th International multi-conference on systems, signals and devices (SSD). IEEE

  34. Torkaman H, Karimi F (2015) Measurement variations of insulation resistance/polarization index during utilizing time in HV electrical machines—a survey. Measurement 59:21–29

    Article  Google Scholar 

  35. Xiao L et al (2013) Influence of aging degree on polarization and depolarization currents of oil-paper insulation. In: 2013 Annual report conference on electrical insulation and dielectric phenomena

  36. Baral A, Chakravorti S (2014) Prediction of moisture present in cellulosic part of power transformer insulation using transfer function of modified debye model. IEEE Trans Dielectr Electr Insul 21(3):1368–1375

    Article  Google Scholar 

  37. Florkowski M, Furgal J (2003) Detection of transformer winding deformations based on the transfer function—measurements and simulations. Meas Sci Technol 14(11):1986

    Article  Google Scholar 

  38. Leibfried T, Feser K (1999) Monitoring of power transformers using the transfer function method. IEEE Trans Power Deliv 14(4):1333–1341

    Article  Google Scholar 

  39. Bigdeli M, Vakilian M, Rahimpour E (2011) A new method for detection and evaluation of winding mechanical faults in transformer through transfer function measurements. Adv Electr Comput Eng 11(2):23–30

    Article  Google Scholar 

  40. Jakob F et al (2003) Use of gas concentration ratios to interpret LTC and OCB dissolved gas data. In: Electrical insulation conference and electrical manufacturing and coil winding technology conference, 2003. Proceedings. IEEE

  41. Sans JR, Bilgin KM, Kelly JJ (1998) Large-scale survey of furanic compounds in operating transformers and implications for estimating service life. In: Conference record of the 1998 IEEE international symposium on electrical insulation, 1998

  42. Stebbins RD, Myers DS, Shkolnik AB (2003) Furanic compounds in dielectric liquid samples: review and update of diagnostic interpretation and estimation of insulation ageing. In: Proceedings of the 7th international conference on properties and applications of dielectric materials, 2003

  43. Dervos CT et al (2006) Dielectric spectroscopy and gas chromatography methods applied on high-voltage transformer oils. IEEE Trans Dielectr Electr Insul 13(3):586–592

    Article  Google Scholar 

  44. Poniran Z, Malek ZA (2007) Life assessment of power transformers via paper ageing analysis. In: 2007 International conference on power engineering, energy and electrical drives

  45. McDermid W, Grant D (2008) Use of furan-in-oil analysis to determine the condition of oil filled power transformers. In: 2008 International conference on condition monitoring and diagnosis

  46. Norazhar AB, Abu-Siada A, Islam SA (2013) Review on chemical diagnosis techniques for transformer paper insulation degradation. In: Power engineering conference (AUPEC), 2013 Australasian Universities

  47. Baird PJ et al (2006) Non-destructive measurement of the degradation of transformer insulating paper. IEEE Trans Dielectr Electr Insul 13(2):309–318

    Article  Google Scholar 

  48. Das N, Abu-Siada A, Islam S (2013) Impact of conducting materials on furan-spectral correlation of transformer oil. In: 2013 Australasian Universities power engineering conference (AUPEC)

  49. Abu-Elanien AE, Salama M (2010) Asset management techniques for transformers. Electr Power Syst Res 80(4):456–464

    Article  Google Scholar 

  50. Saha TK (2003) Review of modern diagnostic techniques for assessing insulation condition in aged transformers. IEEE Trans Dielectr Electr Insul 10(5):903–917

    Article  Google Scholar 

  51. Ali M et al (1996) Measuring and understanding the ageing of kraft insulating paper in power transformers. IEEE Electr Insul Mag 12(3):28–34

    Article  Google Scholar 

  52. Yi C et al (2015) Understanding moisture dynamics and its effect on the dielectric response of transformer insulation. IEEE Trans Power Deliv 30(5):2195–2204

    Article  Google Scholar 

  53. Martin D, Perkasa C, Lelekakis N (2013) Measuring paper water content of transformers: a new approach using cellulose isotherms in nonequilibrium conditions. IEEE Trans Power Deliv 28(3):1433–1439

    Article  Google Scholar 

  54. Ekanayake C et al (2006) Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation. IEEE Trans Power Deliv 21(3):1309–1317

    Article  Google Scholar 

  55. Talib MA et al (2003) Diagnosis of transformer insulation condition using recovery voltage measurements. In: Power engineering conference, 2003. PECon 2003. Proceedings. National. IEEE

  56. Bitam-Megherbi F, Mekious M, Megherbi M (2013) A recovery voltage as non-destructive tool for moisture appreciation of oil impregnated pressboard: an approach for power transformers testing. Int J Electr Eng Inform 5(4):422–432

  57. Bognar A et al (1990) Diagnostic tests of high voltage oil-paper insulating systems (in particular transformer insulation) using DC dielectrometrics. Proc CIGRE 90:33-08

    Google Scholar 

  58. Gubanski SM, Boss P, Csépes G, Houhanessian VD (2003) Dielectric response methods for diagnostics of power transformers. IEEE Electr Insul Mag 19(3):12–18

    Article  Google Scholar 

  59. Saha TK, Purkait P (2004) Investigation of polarization and depolarization current measurements for the assessment of oil-paper insulation of aged transformers. IEEE Trans Dielectr Electr Insul 11(1):144–154

    Article  Google Scholar 

  60. Gafvert U et al (2000) Dielectric spectroscopy in time and frequency domain applied to diagnostics of power transformers. In: Proceedings of the 6th international conference on properties and applications of dielectric materials, 2000

  61. Jamail NAM, Piah MAM, Muhamad NA (2011) Comparative study on conductivity using polarization and depolarization current (PDC) test for HV insulation. In: 2011 International conference on electrical engineering and informatics (ICEEI)

  62. Silva HAP, Bassi W, Diogo ACT (2004) Noninvasive ageing assessment by means of polarization and depolarization currents analysis and its correlation with moisture content for power transformer life management. In: Transmission and distribution conference and exposition: Latin America, 2004 IEEE/PES

  63. Yao ZT, Saha TK (2002) Analysis and modeling of dielectric responses of power transformer insulation. In: Power engineering society summer meeting, 2002 IEEE. IEEE

  64. Jonscher AK (1999) Dielectric relaxation in solids. J Phys D Appl Phys 32(14):R57

    Article  Google Scholar 

  65. Jaya M, Leibfried T, Koch M (2010) Information within the dielectric response of power transformers for wide frequency ranges. In: Conference record of the 2010 IEEE international symposium on electrical insulation (ISEI). IEEE

  66. Liao R et al (2015) Extraction of frequency domain dielectric characteristic parameter of oil-paper insulation for transformer condition assessment. Electr Power Compon Syst 43(5):578–587

    Article  Google Scholar 

  67. Koch M, Prevost T (2012) Analysis of dielectric response measurements for condition assessment of oil-paper transformer insulation. IEEE Trans Dielectr Electr Insul 19(6):1908–1915

    Article  Google Scholar 

  68. Santos E, Elms M, Jabiri Z (2013) End management of power transformers–operational perspective,” unpublished, presented at the Omicron Seminar, Perth, Australia

  69. Liu J et al (2015) Condition evaluation for aging state of transformer oil-paper insulation based on time-frequency domain dielectric characteristics. Electr Power Compon Syst 43(7):759–769

    Article  Google Scholar 

  70. Hui W, Chengrong L, Huimin H (2010) Influence of temperature to developing processes of surface discharges in oil-paper insulation. In: Conference record of the 2010 IEEE international symposium on electrical insulation (ISEI)

  71. Wang H et al (2009) Experimental study on the evolution of surface discharge for oil-paper insulation in transformers. In: IEEE conference on electrical insulation and dielectric phenomena, 2009. CEIDP ’09

  72. Chen X, Cavallini A, Montanari GC (2008) Improving high voltage transformer reliability through recognition of pd in paper/oil systems. In: International conference on high voltage engineering and application, 2008. ICHVE 2008

  73. Sarathi R et al (2014) Influence of harmonic AC voltage on surface discharge formation in transformer insulation. IEEE Trans Dielectr Electr Insul 21(5):2383–2393

    Article  Google Scholar 

  74. Pinpart T, Judd MD (2009) Experimental comparison of UHF sensor types for PD location applications. In: 2009 IEEE electrical insulation conference

  75. Tenbohlen S et al (2008) Partial discharge measurement in the ultra high frequency (UHF) range. IEEE Trans Dielectr Electr Insul 15(6):1544–1552

    Article  Google Scholar 

  76. Yaacob MM, Alsaedi MA, Rashed JR, Dakhil AM, Atyah SF (2014) Review on partial discharge detection techniques related to high voltage power equipment using different sensors. Photonic Sens 4(4):325–337

    Article  Google Scholar 

  77. Boggs S (1990) Partial discharge: overview and signal generation. IEEE Electr Insul Mag 6(4):33–39

    Article  Google Scholar 

  78. Janus P (2012) Acoustic emission properties of partial discharges in the time-domain and their applications. School of Electrical Engineering, Kungliga Tekniska Hogskolan, Stockholm

  79. Howells E, Norton E (1978) Detection of partial discharges in transformers using acoustic emission techniques. IEEE Trans Power Appar Syst PAS–97(5):1538–1549

    Article  Google Scholar 

  80. Akbari A et al (2002) Transfer function-based partial discharge localization in power transformers: a feasibility study. IEEE Electr Insul Mag 18(5):22–32

    Article  Google Scholar 

  81. Niasar MG (2012) Partial discharge signatures of defects in insulation systems consisting of oil and oil-impregnated paper. Royal Institute of Technology (KTH), Stockholm, pp 33–35

  82. Gautschi D, TW, Buchs G (2012) Ultra high frequency (UHF) partial discharge detection for power transformers: sensitivity check on 800 MVA power transformers and first field experience Cigre paper

  83. Yaacob MM, Alsaedi MA, Rashed JR (2014) Review on partial discharge detection techniques related to high voltage power equipment using different sensors. Springer 4(4):325–337

  84. Markalous SM, Tenbohlen S, Feser K (2008) Detection and location of partial discharges in power transformers using acoustic and electromagnetic signals. IEEE Trans Dielectr Electr Insul 15(6):1576–1583

    Article  Google Scholar 

  85. Schwarz R, Muhr M, Pack S (2005) Partial discharge detection in oil with optical methods. In: IEEE International conference on dielectric liquids, 2005. ICDL 2005

  86. Karmakar S, Roy NK, Kumbhakar P (2009) Monitoring of high voltage power transformer using direct optical partial discharge detection technique. Springer 38(4):207–215

    Google Scholar 

  87. Ariastina WG et al (2009) Condition monitoring of power transformer: a field experience. In: IEEE 9th international conference on the properties and applications of dielectric materials, 2009. ICPADM 2009

  88. Blackburn, TR et al (1998) On-line partial discharge measurement on instrument transformers. In: Proceedings of 1998 international symposium on electrical insulating materials, 1998

  89. Akbari A et al (2001) High frequency transformer model for computation of sectional winding transfer functions used for partial discharge localization. In: Proceedings of the 12th international symposium on high voltage engineering, Bangalore, India

  90. Werle P et al (2001) Localisation and evaluation of partial discharges on power transformers using sectional winding transfer functions. In: 12th International symposium on high voltage engineering (ISH), Bangalore, India

  91. Gockenbach E, Borsi H (2008) Transfer function as tool for noise suppression and localization of partial discharges in transformers during on-site measurements. In: International conference on condition monitoring and diagnosis, 2008. CMD 2008

  92. Tenbohlen S et al (2000) Enhanced diagnosis of power transformers using on-and off-line methods: results, examples and future trends. CIGRE paper: 12-204

  93. IEEE guide for diagnostic field testing of electric power apparatus—part 1: oil filled power transformers, regulators, and reactors. IEEE Std 62-1995 (1995), pp 1–64

  94. Transformers—part, 5: ability to withstand short circuit. IEC Standard, 2000: 60076-5

  95. Jayasinghe JASB et al (2006) Winding movement in power transformers: a comparison of FRA measurement connection methods. IEEE Trans Dielectr Electr Insul 13(6):1342–1349

    Article  Google Scholar 

  96. Behjat V, Tamjidi V (2015) Leakage inductance behavior of power transformer windings under mechanical faults. In: Proceedings of the international conference on information technology and computer engineering (ITCE), ITCE’15

  97. Bagheri M et al (2013) Frequency response analysis and short-circuit impedance measurement in detection of winding deformation within power transformers. IEEE Electr Insul Mag 29(3):33–40

    Article  Google Scholar 

  98. Secue JR, Mombello E (2008) Sweep frequency response analysis (SFRA) for the assessment of winding displacements and deformation in power transformers. Electr Power Syst Res 78(6):1119–1128

    Article  Google Scholar 

  99. Patel K et al (2013) Power transformer winding fault analysis using transfer function. In: 2013 Australasian Universities power engineering conference (AUPEC)

  100. Rahimpour E et al (2000) Modellierung der Transformatorwicklung zur Berechnung der Ubertragungsfunktion fur die Diagnose von Transformatoren. Elektrie 54(1–2):18–30

    Google Scholar 

  101. Dick EP, Erven CC (1978) Transformer diagnostic testing by frequency response analysis. IEEE Trans Power Appar Syst PAS–97(6):2144–2153

    Article  Google Scholar 

  102. Pham DAK et al (2012) FRA-based transformer parameters at low frequencies. In: ICHVE 2012—2012 international conference on high voltage engineering and application 2012

  103. Prevost T (2015) Power transformer insulation diagnostics, Omicron Seminar, Perth, WA

  104. Birlasekaran S, Fetherston F (1999) Off/on-line FRA condition monitoring technique for power transformer. IEEE Power Eng Rev 19(8):54–56

    Article  Google Scholar 

  105. ANSI/IEEE C57.91, IEEE guide for loading mineral-oil-immersed transformers (1995)

  106. John J, Winders J (2002) Allentown. Marcel Dekker Inc, Pennsylvania

  107. IEEE guide for loading mineral-oil-immersed transformers, IEEE Std C57.91 (1996)

  108. Bai CF, Gao WS, Liu T (2013) Analyzing the impact of ambient temperature indicators on transformer life in different regions of Chinese Mainland. Sci World J 2013:125896

    Google Scholar 

  109. Schaut A, Autru S, Eeckhoudt S (2011) Applicability of methanol as new marker for paper degradation in power transformers. IEEE Trans Dielectr Electr Insul 18(2):533–540

    Article  Google Scholar 

  110. Wouters PAAF, Schijndel AV, Wetzer JM (2011) Remaining lifetime modeling of power transformers: individual assets and fleets. IEEE Electr Insul Mag 27(3):45–51

    Article  Google Scholar 

  111. Gorgan B et al (2012) Calculation of the remaining lifetime of power transformers paper insulation. In: 2012 13th International conference on optimization of electrical and electronic equipment (OPTIM)

  112. Martin D et al (2015) An updated model to determine the life remaining of transformer insulation. IEEE Trans Power Deliv 30(1):395–402

    Article  Google Scholar 

  113. Emsley AM (2000) Degradation of cellulosic insulation in power transformers. Part 3: effects of oxygen and water on ageing in oil. IEE Proc Sci Meas Technol 147(3):115–119

    Article  Google Scholar 

  114. M E (2015) Life cycle management of power transformers: results and discussion of case studies. IEEE Trans Dielectr Electr Insul 22(4):2379–2389

    Article  Google Scholar 

  115. Oommen TV, Prevost TA (2006) Cellulose insulation in oil-filled power transformers: part II maintaining insulation integrity and life. IEEE Electr Insul Mag 22(2):5–14

    Article  Google Scholar 

  116. Gockenbach E et al (2012) Life time prediction of power transformers with condition monitoring. In: 44th International conference on large high voltage electric systems 2012

  117. An international survey of failures in large power transformers in service, CIGRE Working Group 05, Electra, no. 88, 21–48 (1983)

Download references

Author information

Authors and Affiliations

Authors

Corresponding author

Correspondence to Md Mominul Islam.

Rights and permissions

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Islam, M.M., Lee, G. & Hettiwatte, S.N. A review of condition monitoring techniques and diagnostic tests for lifetime estimation of power transformers. Electr Eng 100, 581–605 (2018). https://doi.org/10.1007/s00202-017-0532-4

Download citation

  • Received:

  • Accepted:

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s00202-017-0532-4

Keywords

Navigation