Elsevier

Energy and Buildings

Volume 179, 15 November 2018, Pages 183-199
Energy and Buildings

Quantifying energy losses in hot water reheat systems

https://doi.org/10.1016/j.enbuild.2018.09.020Get rights and content

Highlights

  • New method to estimate energy use and distribution losses in hot water reheat systems.

  • Accurate to within 14% as assessed in case study of 11,000 m2 office building.

  • Gas to intentional reheat energy conversion shows 79% loss, incl. 44% distribution loss.

  • High boiler losses for these systems in practice due to ultra-low part load operation.

  • Electric reheat and PV cheaper and more efficient than current practice in many cases.

Abstract

We developed a new method to estimate useful versus wasted hot water reheat energy using data obtained from typically installed instrumentation that applies to all pressure independent VAV terminal units with discharge air temperature sensors. We evaluated the method using a year of 1 min interval data for a 11,000 m2 building with 98 terminal reheat units, and found a 14% upper bound for the uncertainty associated with this method. We found that just 21% of gas energy is converted to useful reheat energy in this building. The distribution losses alone were 44% of the heat output from the boiler. The results raise questions regarding the tradeoffs between hot water heating systems, which have significant distribution losses, and electric heating systems, which effectively have zero distribution losses. In this building, and likely many others, an electric reheat system supplied by a small photovoltaic panel system would have a lower operating energy cost and a lower initial cost than the hot water reheat system. Further investigations using this method will be relevant to designers and standards developers in deciding between electric and hot-water reheat, particularly for modern designs using dual-maximum controls and low minimum airflow setpoints.

Introduction

Where a central heating ventilation and air conditioning (HVAC) system supplies multiple zones with the same temperature air, heating coils are needed at the terminal units (i.e. at the zone or room level) in zones that may require heating when there is a demand for cooling elsewhere in the building. An air handling unit (AHU) single-duct system serving multiple zones with variable air volume (VAV) terminal units is a very common type of HVAC system in commercial buildings. Each terminal unit has a damper to control airflow to meet ventilation air requirements and so that it can increase airflow to provide cooling as needed up to its design maximum flow rate. In all but the warmest climates, perimeter zones require heating coils at the terminal units. However, heating coils are also often needed in interior zones to ensure that these zones are not overcooled when supplying (typically cool) ventilation air. For example, when the supply air leaving the AHU must be quite cool to meet a need for cooling in the building (e.g. a west facing zone, operating at maximum air flow), this supply air temperature may be too low for other (e.g. interior) zones served by that AHU. These terminal unit heating coils are typically known as ‘reheat coils’ as there are some times of the year when the AHU has cooled the supply air, only to then ‘reheat’ it at some terminal units. Either electricity or a hot water distribution system serves as the energy source for these coils. Hot water reheat systems, typically served by a gas-fired boiler, are more widely used in buildings because of lower utility costs than for electric reheat systems. Electric reheat is even prohibited in some codes and standards (such as California Title 24 [1]).

For context, Zhang et al. [2] recently concluded a large study of distribution losses for a conceptually similar type of system: open-loop centralized domestic hot water recirculation systems fed by natural gas boilers. The results showed that the delivered hot water energy in 28 different buildings averaged just 35% of the source gas energy consumption [2], that is, there was a 65% loss in the system, due in equal part to distribution losses and losses at heating equipment. There are numerous studies [3], [4], [5], [6], [7], [8], [9], [10], [11], [12], [13] of heat transfer and demand within open-loop domestic hot water systems for a range of different applications in both commercial and residential buildings. The overall system efficiency and distribution system losses vary very widely depending on design and application. Chapter 50 of the ASHRAE handbook of applications [14] summarizes this well as “Energy losses from hot-water distribution systems usually amount to at least 10% to 20% of total hot-water system energy use in most potable water-heating systems [3], and are often as high as 50%; losses of over 90% have been found in some installations [15]”. This includes both heat lost from the distribution system, as well as water and heat wasted at the fixture as the user waits for water to reach a usable temperature. These findings show that the overall system efficiency is far lower than expected based on idealized analysis of these systems.

In comparison, though there is no water waste in a closed-loop reheat system, many losses are similar to open loop domestic hot water systems. In a closed-loop hot water system used for primary heating, where the majority of the building is operating in heating mode, these losses are of less concern as long as the losses occur within the building envelope. Though they may cause control problems (e.g. overheating in some zones), the losses still contribute to heating the building overall. In contrast, for reheat systems, the demand for heat is typically only from a relatively small number of zones in the building, under conditions that vary widely based on the time of day, supply air temperature, heat load in the zone, minimum airflow rates, heat transfer through the envelope, etc. Reheat demand often occurs during times of the day and year in which the majority of the zones in the building require cooling, or in large buildings where the interior zones always require cooling independent of outdoor weather conditions. In this case, the losses will also be a significant component of overall hot water system efficiency.

Lastly, recently developed control strategies used to improve the energy efficiency of VAV systems, such as those described and demonstrated in [16], [17], [18], [19], [20] and recently formalized in ASHRAE Guideline 36 [21], successfully avoid most unnecessary reheat energy. These strategies reduce the minimum airflow setpoint at the VAV terminal unit to a more appropriate level. Historically, designers have defined this as a fixed percentage of the design maximum airflow, typically 30%, or often even higher (e.g. 50%) for VAV terminal units with reheat coils that use single-maximum control logic.1 Using dual-maximum control logic [18] or time-averaged ventilation [20] allows the minimum to be set to the correct value—the design ventilation airflow requirement for the zone.2 Many of the heating system losses described above are constant and do not vary with the need for reheat in the building. Thus, they become proportionally more significant when the overall useful reheat demand decreases.

In this paper we focused on closed-loop systems serving reheat coils at variable air volume (VAV) terminal units, commonly known as ‘VAV boxes’. We performed a thorough literature review of likely sources of publications on this topic and were unable to find prior studies that analyzed this specific case. The energy wasted within these systems occurs due to a number of factors:

  • Heat lost through insulated and uninsulated piping and fixtures, both during flow conditions and when non-flowing water reaches steady state with the surrounding environment. Hiller [3] describes these losses in detail and illustrates them using a number of example calculations.

  • Heat lost by passing valves unnecessarily supplying hot water to a reheat coil, a problem that is unique to the nature of hot-water heating systems of any kind.

  • Electrical motor losses serving circulation pumps.

  • Boiler combustion, standby and parasitic losses.

In contrast, electric reheat systems have minimal distribution losses, no passing valves, no boiler losses, and lower initial installation costs, but typically have much higher unit energy costs.

We formalized the primary research questions that we wished to answer as: (1) How do we cost-effectively quantify intentional reheat energy use in buildings with hot water reheat systems; (2) What are the distribution losses in a real building; and (3) Under what conditions do the initial cost and operating energy cost tradeoffs favor electric reheat?

Section snippets

Description

We performed a case study of a 5 story, 11,000 m2 office building in the California Bay Area. The Bay Area is a Koppen Csb climate zone (California climate zone 3, ASHRAE climate zone 3C) characterized by dry, warm summers and mild winters. Constructed in 1999, the building is predominately open plan with some enclosed offices and conference rooms along the perimeter, and a central core of services and conference rooms. The window-to-wall-ratio is approximately 0.6 on the first floor and 0.45

Overview

We aimed to quantify the losses in the hot water distribution system by measuring the hot water energy supplied by the boiler and comparing this to the intentional reheat energy use, aggregated for every zone—i.e. at each reheat coil. We calculated the heat supplied from the boiler by performing a heat balance calculation using the water flow rate and the boiler supply and return temperatures, assuming the standard properties for water.

We used a novel approach to calculate the amount of

Analysis of the hot water distribution system

The analysis considered operating and non-operating hours separately for the boiler and AHU variables. We defined the operating hours as when the AHU fan speed is greater than zero, and defined all other intervals as non-operating hours. Typically, operating hours range from 4:00 a.m. to 5:00 p.m. during weekdays—the start time varies slightly across the year due to an optimal start algorithm. Table 1 compares summary statistics for boiler and AHU variables, subset by operating and

Assessing hot water reheat distribution losses

Table 1 shows that the distribution losses during operating hours (where some reheat coil valves are open) and non-operating hours (where almost no reheat coil valves are open, and the AHUs do not run) were quite similar. The distribution losses were slightly higher during operating hours, which we expect as there is additional heat transfer from the piping connecting the main trunk piping to the reheat coil valves when those valves are open than when they have been closed for an extended

Conclusions

This paper provides a method for estimating intentional reheat energy consumption which uses only the data available from sensors typically installed with a modern VAV system. We demonstrated and validated that method on a large office building over a one year period. For the first time to date, we assessed the overall efficiency of the reheat system in a real building, quantifying intentional reheat energy use, hot water distribution losses and boiler efficiency. In the case study building,

Acknowledgments

We wish to sincerely thank the building owners and operators for allowing us access to the data. The Center for the Built Environment (CBE) at the University of California, Berkeley and the California Energy Commission funded this work. This work was conceptualized and initiated as part of a California Energy Commission (CEC) project entitled “Changing the Rules” (contract number PIR-12-026).

References (43)

  • C.C. Hiller

    Hot water distribution system piping time, water, and energy waste–Phase II: test results

    ASHRAE Trans.

    (2008)
  • C.C. Hiller

    Hot-water distribution system piping heat loss factors–Phase III: test results

    ASHRAE Trans.

    (2011)
  • C.C. Hiller

    Hot water distribution system piping heat loss factors–Phase I: test results

    ASHRAE Trans.

    (2006)
  • C.C. Hiller

    Hot water distribution system piping heat loss factors, both in air and buried- phase ii test results

    ASHRAE Trans.

    (2008)
  • J.D. Lutz

    Water and energy wasted during residential shower events: findings from a pilot field study of hot-water distribution systems

    ASHRAE Trans.

    (2012)
  • J.D. Lutz

    estimating energy and water losses in residential hot water distribution systems

    ASHRAE Trans.

    (2005)
  • J.D. Lutz et al.

    Pilot phase of a field study to determine waste of water and energy in residential hot-water distribution systems

    ASHRAE Trans.

    (2011)
  • Handbook of Applications

    (2015)
  • C. Hiller et al.

    Field test comparison of a potable hot water recirculation-loop system vs. point-of-use electric resistance water heaters in a high school

    ASHRAE Trans.

    (2005)
  • M. Hydeman et al.

    Advanced Variable Air Volume System Design Guide

    (2003)
  • E. Arens et al.

    ASHRAE Research Project 1515 - Thermal and air quality acceptability in buildings that reduce energy by reducing minimum airflow from overhead diffusers

    (2012)
  • Cited by (7)

    • Apartment related energy performance gap – How to address internal heat transfers in multi-apartment buildings

      2020, Energy and Buildings
      Citation Excerpt :

      Staircases were also not accounted for in the model for the calculation of the energy demand for the apartments, leading to slightly biased internal and external heat transmission losses. Regarding the data, no information was available on the heat transfer coefficients for internal walls, so we took a rather conservative estimate based on the available information [64–73]. Data on climate conditions like wind speed and relative humidity, which might affect both the heat transmission losses and behaviour [41–90] were likewise not available.

    View all citing articles on Scopus
    View full text