Article

Energy Performance Investigation of a Direct Expansion Ventilation Cooling System with a Heat Wheel

Department of Building Service Engineering and Process Engineering, Faculty of Mechanical Engineering, Budapest University of Technology and Economics, Muegyetem rkp. 3., H-1111 Budapest, Hungary
Energies 2019, 12(22), 4267; https://doi.org/10.3390/en12224267
Submission received: 11 October 2019 / Revised: 4 November 2019 / Accepted: 7 November 2019 / Published: 8 November 2019
(This article belongs to the Special Issue Evaluation of Energy Efficiency and Flexibility in Smart Buildings)

Abstract

:
Climate change is continuously bringing hotter summers and because of this fact, the use of air-conditioning systems is also extending in European countries. To reduce the energy demand and consumption of these systems, it is particularly significant to identify further technical solutions for direct cooling. In this research work, a field study is carried out on the cooling energy performance of an existing, operating ventilation system placed on the flat roof of a shopping center, located in the city of Eger in Hungary. The running system supplies cooled air to the back office and storage area of a shop and includes an air-to-air rotary heat wheel, a mixing box element, and a direct expansion cooling coil connected to a variable refrigerant volume outdoor unit. The objective of the study was to investigate the thermal behavior of each component separately, in order to make clear scientific conclusions from the point of view of energy consumption. Moreover, the carbon dioxide cross-contamination in the heat wheel was also analyzed, which is the major drawback of this type heat recovery unit. To achieve this, an electricity energy meter was installed in the outdoor unit and temperature, humidity, air velocity, and carbon dioxide sensors were placed in the inlet and outlet section of each element that has an effect on the cooling process. To provide continuous data recording and remote monitoring of air handling parameters and energy consumption of the system, a network monitor interface was developed by building management system-based software. The energy impact of the heat wheel resulted in a 624 kWh energy saving and 25.1% energy saving rate for the electric energy consumption of the outdoor unit during the whole cooling period, compared to the system without heat wheel operation. The scale of CO2 cross-contamination in the heat wheel was evaluated as an average value of 16.4%, considering the whole cooling season.

1. Introduction

The use of environmental control systems has significantly increased in the building sector in order to reduce the energy consumption of heating, ventilation, and air-conditioning (HVAC) systems [1]. Air handling units (AHUs) are one of the most complex building service systems [2], and can include heating, cooling, humidifier, mixing element, and heat recovery units, in order to provide the required indoor air quality and thermal comfort in conditioned spaces [3].
In a typical AHU, chilled water in the cooling coils cools the air, and hot water (or steam) in the heating coils heats the air, in order to maintain the desired temperature of the supply [4]. The supply and return fans assist in moving the air for heat exchange, as well as circulating it in the HVAC system at the required flow rate [5]. Several components are part of a typical system, i.e., the chiller, the boiler, the supply and return fans, and the water pump that consumes a lot of energy [6].
Direct expansion ventilation units are becoming more commonly used central air-conditioning technical solutions, in which a refrigerant is directly delivered to the cooling (and heating) coil [7]. These systems have the potential to save cooling and heating energy use, since they do not require any water pumps for their operation, compared to water-based central air conditioning systems [8,9].
Developers are working really hard to minimalize the energy consumption of their developed devices; however, there are many imperfections in the actual available product catalogues, technical data, and technical support service systems, especially for the annual energy designing provided by the ventilation producers for building service and energy design engineers [10,11]. Therefore, it would be particularly significant to have measured and recorded data obtained from field studies [12,13], which may be utilized in the course of design work, and which would allow a proper estimation of the expected realizable annual energy consumption of air handling elements in the function of the temperature and relative humidity of ambient and indoor air and operating parameters [14].
Stamatescu et. al [15] presented the implementation and evaluation of a data mining methodology based on collected data from a more than one-year operation. The case study was carried out on four AHUs of a modern campus building for preliminary decision support for facility managers. The results are useful for deriving the behavior of each piece of equipment in various mode of operation and can be built upon for fault detection or energy efficiency applications. The imperfection of their work is the missing data for air condition parameters (temperature and humidity) between the coils and mixing box; before and after the fans, which cannot be neglected, since the electrical motor of the fans increases the air temperature and decreases the relative humidity; and the air volume flow rate, which changes during the operation. All these missing parameters have a significant effect on the energy efficiency of the ventilation system.
Hong et. al [16] conducted a case study on a running AHU for data-driven predictive model development. In order to develop the optimal model, input variables, the number of neurons and hidden layers, and the period of the training data set were considered. The results and conclusions presented for the one-year field study could have much better reflected the reality from the view point of energy performance, if further temperature and relative humidity sensors had been placed between the coils and humidifier element, before and after the fans. Only focusing on energy performance data recording is not enough, since the desired indoor air quality and thermal comfort are also significant parameters that need to be considered. To draw a more exact conclusion from this point of view, the CO2 parameter should also have been monitored and recorded in the outdoor air inlet (OA) and supply air outlet (SA) sections in the investigated AHU.
Based on a literature review of the field, there are some case studies in which the heat recovery unit has also been considered in the ventilation system. Noussan et. al [17] presented results obtained from an operation data analysis of an AHU serving a large university classroom. The main drivers of energy consumption are highlighted, and the classroom occupancy is found to have a significant importance in the energy balance of the system. The availability of historical operation data allowed a comparison of the actual operation of the AHU and the expected performance from nominal parameters to be performed. Calculations were made considering the operation analysis of the heat recovery unit over different years; however, the existing system does not include any heat or energy recovery devices, so there are no exact measured data from this point of view.
Bareschino et. al [18] compared three alternative hygroscopic materials for desiccant wheels considering the operation of the air handling unit they are installed in. Their results demonstrated that a primary energy saving of about 20%, 29%, and 15% can be reached with silica-gel, milgo, and zeolite-rich tuff desiccant wheel-based air handling units, respectively. The results were given based on a simulation and there is no exact measured data, which would be significant for making precise and clear energetic conclusions.
In this work, a field study is carried out on an existing, operating ventilation system that includes an air-to-air rotary heat wheel, a mixing box element, and a direct expansion cooling coil connected to a variable refrigerant volume outdoor unit. One of the main objectives of the present paper is to investigate the cooling energy performance and thermal behavior of each air handling component separately. To achieve this, an advanced data recording and remote monitoring system was considerately developed by building management system-based software. The system includes an electricity energy meter installed in the outdoor unit, as well as temperature, humidity, air velocity, and CO2 sensors placed in the inlet and outlet section of all the air handling elements that have an effect on the cooling process. The purpose of the CO2 measurements was to investigate the CO2 cross-contamination, which occurs from the exhaust air flow to the supply air flow in the air-to-air rotary heat wheel, resulting in indoor air quality degradation. The novelty of this research is the accurate determination of the seasonal effectiveness and the energy saving impact of the heat wheel on the electric energy consumption of the outdoor unit. Moreover, the relative average and maximum value of CO2 cross-contamination in the rotary heat recovery using the developed measurement system in the cooling period are presented. A further innovation in this study is the analytical evaluation method developed, which shows a good agreement between the calculated and measured energy consumption.

2. Materials and Methods

The selected air handling unit (AHU) is located on the flat roof of a shopping center, located in the city of Eger in Hungary, which has supplied fresh air to the back-office and storage area of a shop since 2017.

2.1. Description of the Investigated Central Ventilation System

The main air handling components of the system are an air-to-air rotary heat wheel, a mixing box element, and direct expansion cooling/heating (DX) coil connected to a variable refrigerant volume outdoor unit. Figure 1 shows the elements of the investigated AHU.
The specification of the AHU can be seen in Table 1.
Figure 2 shows the outdoor unit which is connected with refrigerant pipes to the DX coil and is located in the AHU.
Technical data of the unit can be seen in Table 2.
Table 3 shows the specification of the air-to-air recovery heat wheel in the cooling period.

2.2. Description of the Developed Measurement System

In total, six temperature and relative humidity sensors, three CO2 sensors and three air velocity sensors were placed in the inlet and outlet section of each air handling element and an electricity energy meter was installed in the outdoor unit. The placement of the measurement points can be seen in Figure 3. The technical data of the installed sensors and instrument can be read in Table 4.
The recording of the measured data took place in an hourly period. With regards to the measurement accuracy, temperature sensors are normally used with a ±0.4 °C accuracy, humidity sensors with a ±3% accuracy, an air velocity sensor with a ±0.2 m/s accuracy, carbon dioxide sensors with a ±50 ppm accuracy, and an electric energy meter with a 1% of full scale accuracy. Among the monitoring air handling data, the air temperature and relative humidity data of the inlet and outlet sections of the DX cooling coil, energy recovery unit, and outdoor were used to investigate the energy performance and thermal behaviour of these air handling elements in the AHU in the cooling season.
The specification of the sensors and electricity energy meter used for monitoring of the investigated AHU can be seen in Table 4.
For the monitoring and recording of the various air condition parameters and the electrical energy consumption of the outdoor unit, the CentraLine Building Management System (BMS) software (version 2019) solution from Honeywell was implemented on a central server. Figure 4 shows a picture of the target building, along with a representative BMS screen for the investigated air handling unit.
Access to the BMS software was remotely enabled. Within this technical context, the necessary data were collected for this field study. Data were collected online at hourly intervals, saved, and stored on a computer from a distance.

3. Evaluation of the Data Recorded

To investigate the energy performance of the AHU, using the measurements, the following mathematical approaches were implemented.

3.1. Calculation Formulas for Measured Data Evaluation

Using the measured air temperature and relative humidity data, the specific humidity could be calculated to obtain the enthalpy of the air. To achieve this, the water vapor saturation pressure (Pws) was first calculated with Equation (1) [20]:
P w s = A · 10 ( m t t + t n ) · 100 ,
where Pws is the saturation pressure of the water vapor in Pa; t is the air temperature in °C; and A, m, and tn are constant values in -. Since the temperature range during the measurements was between −20 and +50 °C, the constant values (in 0.083% maximum error) were as follows: A = 6.116441; m = 7.591386; tn = 240.7263 [20]. The constant value of 100 in Equation (1) represents the conversion of the saturation pressure of water vapor from hPa to Pa.
To obtain the moisture content, the partial pressure of water vapor in the air at a given relative humidity was also calculated with Equation (2) [20]:
P w = P w s · R H 100 ,
where Pw is the partial pressure of water vapor in Pa and RH is the relative humidity of the air in %. The constant value of 100 in Equation (2) represents the conversion of relative humidity from % to -.
The moisture content was calculated with Equation (3) [21]:
x = 0.622 · P w P o P w ,
where x is the moisture content of the air in kg/kg, Po is the barometric pressure in Pa, and the 0.622 constant value is the molecular weight ratio of water vapor to dry air.
The enthalpy was calculated with Equation (4) [21]:
h = c p a · t + x · ( c p w · t + 2500 ) ,
where h is the enthalpy of the air in kJ/kg, cpa is the specific heat of air at constant pressure in kJ/(kg·°C), cpw is the specific heat of water vapor at constant pressure in kJ/(kg·°C), and the constant value of 2500 represents the evaporation heat in kJ/(kg·°C).

3.2. Formulas for Energy Calculations

Considering the fact that there is balanced ventilation, the effectiveness values of the heat wheel were determined from the air temperature measured values using Equation (5) [22,23]:
ε s = ( t H W S t o ) ( t H W E t o ) ,
where εS is the real sensible effectiveness of the heat wheel given by the measured data in -, tHWS is the air temperature in the supply outlet section of the heat wheel in °C, tHWE is the air temperature in the exhaust inlet section of the heat wheel in °C, and to is the ambient air temperature which is equal to the air temperature in the supply inlet section of the heat wheel in °C.
To get information about the seasonal energy performance of the heat recovery during the cooling period, the average of the sensible effectiveness was calculated with Equation (6):
ε ¯ s _ A V = i = 1 n ε s _ i n ,
where ε ¯ s _ A V is the average of the sensible effectiveness of the heat wheel given by the measured data in the cooling season in - and n is the number of measurements.
The maximum value of the sensible effectiveness was also analyzed during the whole cooling season, which was calculated with Equation (7):
ε s _ M A X = M A X   ( ε s _ i ε s _ n ) ,
where ε ¯ s _ M A X is the maximum value of the sensible effectiveness of the heat wheel given by the measured data in the cooling season in -.
To calculate the energy saving of the heat wheel in the cooling season, Equation (8) was used:
Q H W _ s a v e d = m ˙ s · ( h o h H W S ) · τ ,
where QHW_saved is the energy saving of the heat wheel in kWh; m ˙ s is the air mass flow rate delivered by the fans in kg/s, which is calculated by the multiplication of the measured air velocity in m/s and the internal cross-section of air duct in 0.7398 m2 and approached a 1.2 kg/m3 constant air density; ho is the ambient air enthalpy which is equal to the air enthalpy in the supply inlet section of the heat wheel in kJ/kg; hHWS is the air enthalpy in the supply outlet section of the heat wheel in kJ/kg; and τ is the time in hours. The average air volume flow rate was evaluated as 1060 m3/h during the cooling season.
To calculate the cooling energy consumption of the DX coil, Equation (9) was used:
Q D X _ H W = m ˙ s · ( h H W S h D X ) · τ ,
where QDX_HW is the cooling energy consumption of the DX coil in kWh, and hDX is the air enthalpy in the supply outlet section of the DX coil in kJ/kg, which is equal to the supply air condition.
In order to investigate more the energy saving impact of the heat wheel on the DX coil, the cooling energy consumption of DX coil was also determined by Equation (10), neglecting the air-to-air rotary heat wheel operation, when the DX coil directly cools the hot ambient air to the supply air conditions.
Q D X _ W O _ H W = m ˙ s · ( h o h D X ) · τ ,
where QDX_WO_HW is the cooling energy consumption of the DX coil without the heat wheel operation in kWh.
The calculated electric energy consumption of the outdoor unit was calculated with Equation (11):
P V R V _ H W = Q D X _ H W E E R ,
where PVRV_HW is the calculated electric energy consumption of the outdoor unit with the heat wheel operation in kWh, and EER is the energy efficiency ratio, given by the producer in -.
Moreover, the real electric energy consumption of the outdoor unit (PVRV_HW_M) was also measured during the cooling season, in order to see the agreement between values of the measured data and calculations using the recorded air condition parameters (PVRV_HW). The difference between the measured and calculated electric energy consumption was determined with Equation (12):
Δ P V R V _ H W = P V R V _ H W _ M P V R V _ H W ,
where ΔPVRV_HW is the difference between the measured and calculated electric energy consumption of the outdoor unit with the heat wheel operation in kWh.
The rate of deviation of the measured and calculated electric energy consumption of the outdoor unit related to the measured data was calculated with Equation (13):
Δ P V R V _ H W _ R E L = Δ P V R V _ H W P V R V _ H W · 100 ,
where ΔPVRV_HW_REL is the rate of deviation of the measured and calculated electric energy consumption of the outdoor unit in %.
The electric energy consumption of the outdoor unit without the heat wheel operation was calculated with Equation (14):
P V R V _ W O _ H W = Q D X _ W O _ H W E E R ,
where PVRV_WO_HW is the electrical energy consumption of the outdoor unit without the heat wheel operation in kWh when it directly cools the hot ambient air to the supply air conditions via the DX coil during the cooling season.
The energy saving of the heat wheel in terms of the electric energy consumption of the outdoor unit was calculated with Equation (15):
Δ P V R V _ H W _ s a v e d = P V R V _ W O _ H W P V R V _ H W ,
where ΔPVRV_HW_saved is the amount of energy saved by the heat wheel in terms of the calculated electric energy consumption of the outdoor unit compared to that without the heat recovery operation in kWh.
The energy saving impact of the heat wheel on the electric energy consumption of the outdoor unit, compared to the system without the heat wheel operation, was calculated with Equation (16):
Δ P V R V _ H W _ s a v e d _ R E L = Δ P V R V _ H W _ s a v e d P V R V _ W O _ H W · 100 ,
where ΔPVRV_HW_saved_REL is the energy saving rate of the heat wheel for the electric energy consumption of the outdoor unit, compared to the system without heat the wheel operation, in %.
The value of the actual energy efficiency ratio of the outdoor unit given obtained the field study was determined with Equation (17) for the investigated cooling season to compare the data provided by the producer:
E E R M = Q D X _ H W P V R V _ H W _ M · 100 ,
where EERM is the evaluated energy efficiency ratio (-) based on the measurement during the whole investigated cooling season.

3.3. Formulas for Carbon Dioxode Cross-Contamination in the Heat Wheel

The scale of carbon dioxide (CO2) cross-contamination in the air-to-air rotary heat recovery wheel was also investigated by measurements in the heat wheel during the operation of the air handling unit in the cooling period. To achieve this, the CO2 concentration difference between the supply inlet and outlet sections of the heat wheel was first determined with Equation (18):
Δ C C O 2 _ c r o s s = C C O 2 _ H W S C C O 2 _ o ,
where ΔCCO2_cross is the scale of the CO2 cross-contamination in the heat wheel in a given hour in ppm; CCO2_HWS is the CO2 concentration in the supply outlet section of the heat wheel in ppm; and CCO2_o is the CO2 concentration of the ambient air in ppm, which is equal to the CO2 concentration in the supply inlet section of the heat wheel in ppm.
Having completed the measurements, the average of the CO2 cross-contamination values was taken, and the ratio of the result and the supplied average CO2 concentration was calculated by Equation (19):
Δ C ¯ C O 2 _ c r o s s _ A V = i = 1 n Δ C C O 2 _ c r o s s _ i n ,
where ΔCCO2_cross_AV is the average of the CO2 cross-contamination values in ppm and n is the number of measurements.
Since CO2 cross-contamination occurs from the exhaust section to the supply section in the heat wheel, the average of the measured CO2 values in the exhaust inlet section of the heat wheel was also calculated with Equation (20) using the data measured:
C ¯ C O 2 _ H W E _ A V = i = 1 n C C O 2 _ H W E _ i n ,
where CCO2_HWE_AV is the average value of the CO2 concentration in the exhaust inlet section of the heat wheel in ppm and n is the number of measurements.
Equation (21) was used to obtain the relative average of differences:
Δ C ¯ C O 2 _ R E L = Δ C ¯ C O 2 _ c r o s s _ A V C ¯ C O 2 _ H W E _ A V · 100 ,
where ΔCCO2_REL is the relative average of CO2 cross-contamination in %, considering the CO2 concentration content in the exhaust inlet section of the heat wheel in ppm.
The maximum value of CO2 cross-contamination was also analyzed during the whole cooling season, which was calculated with Equation (22):
C C O 2 _ R E L _ M A X = [ M A X   ( C C O 2 _ c r o s s _ i C C O 2 _ H W E _ i C C O 2 _ c r o s s _ n C C O 2 _ H W E _ n ) ] · 100 ,
where CCO2_REL_MAX is the maximum value of CO2 cross-contamination in the heat wheel in the cooling season given by the measured data in %.

4. Results and Discussion

The reference period of the study is the year 2019, more specifically, the cooling period from June 1st to August 31st for a total of 92 days and 25,296 data samples for each of the used measurement points. The AHU is intermittently operated 12 h/day from 8:00 till 20:00 7 days/week. Since this research work focused on the ventilation energy saving of the heat recovery unit’s DX cooling coil, the mixing box was shut off during the data recording.
The air handling parameters obtained from the field study for the investigated AHU are illustrated in Figure 5, Figure 6 and Figure 7 with a monthly timescale. Since the ambient air temperature was the highest in June during the whole cooling season, this relevant month was selected to present the measured data resulting from the data collection.
Figure 5 shows the temperature of the outdoor air (to), the air in the supply outlet sections of the heat wheel (tHWS) and DX coil (tDX), and the exhaust inlet section of the heat wheel (tHWE) over time at hourly intervals in June.
Considering the hottest periods in the cooling season, the ambient air temperature decreased by about 4–5 °C due to the pre-cooling effect of the heat wheel, and by an additional 18–20 °C, provided by air cooling of the DX coil.
Figure 6 shows the measured relative humidity of the outdoor air (RHo), the air in the supply outlet sections of the heat wheel (RHHWS) and DX coil (RHDX), and the exhaust inlet section of the heat wheel (RHHWE) over time at hourly intervals in June.
The ambient air relative humidity decreased by about 60% due to the air cooling process. In this way, the supplied air relative humidity was around 90%.
Figure 7 shows the enthalpy of the outdoor air (ho), the air in the supply outlet sections of the heat wheel (hHWS) and DX coil (hDX), and the exhaust inlet section of the heat wheel (hHWE) over time at hourly intervals in June.
Considering the hottest periods in the cooling season, the ambient air enthalpy decreased by about 8–10 kJ/kg due to the pre-cooling effect of the heat wheel, and by an additional 30–35 kJ/kg, provided by air cooling of the DX coil.
Figure 8 shows the sensible effectiveness data (εs) for the outdoor air temperature in June.
Based on the results, the average sensible effectiveness of the heat wheel was 79.6% during the whole cooling season and the maximum value of 97.6% was recorded in June.
Figure 9 shows the energy saving of the air-to-air rotary heat wheel (QHW_saved) in terms of the energy consumption of the DX coil, and the cooling energy consumption of the DX coil with the heat wheel operation (QDX_HW) and without the heat wheel operation (QDX_WO_HW), when the DX coil directly cools the hot ambient outdoor air to the supply air conditions during the cooling season.
Based on the results, the energy saving of the heat wheel was 2491 kWh in terms of the energy consumption of the DX coil, the cooling energy consumption of the DX coil with the heat wheel operation was 7434 kWh, and that without the heat wheel operation was 9926 kWh.
Figure 10 shows the electric energy consumption of the outdoor unit based on the direct real electric energy consumption measurements (PVRV_HW_M) and the calculations made using the recorded air condition parameters with (PVRV_HW) and without the heat wheel operation (PVRV_WO_HW) for the whole cooling period.
The real electric energy consumption of the outdoor unit based on the measurements was 1889 kWh and the calculations resulted in 1863 kWh consumption with and 2488 kWh consumption without the heat wheel operation for the whole cooling period.
Since the difference (ΔPVRV_HW) is only 26 kWh and rate of deviation (ΔPVRV_HW_REL) is 1.36% between the values of the measured and calculated electric energy consumption of the variable refrigerant volume (VRV) outdoor unit with the heat wheel operation, Figure 10 shows very good agreement between the experimental and numerical results. The evaluated energy efficiency ratio is 3.94 based on the measurements (EERM) conducted for the whole investigated cooling season, which is only 0.05 less than the value of 3.99 given by the producer. The energy impact of the heat wheel results in 624 kWh energy being saved (ΔPVRV_HW_saved), which is equivalent to a 25.1% energy saving rate (ΔPVRV_HW_saved_REL) in terms of the electric energy consumption of the outdoor unit for the whole cooling period, compared to the system without the heat wheel operation.
Figure 11 shows the measured CO2 concentration of the outdoor air (CCO2_o), the air in the supply outlet section of the heat wheel (CCO2_HWS), and the exhaust inlet section of the heat wheel (CCO2_HWE) over time at hourly intervals in June. There are a few hours in Figure 11 when the recorded CO2 values of the air were lower in the supply outlet section than in the exhaust inlet section of the heat wheel, probably due to the uncertainties and transient response characteristics of the CO2 sensors.
Having completed the measurements of the whole cooling period, the average CO2 cross-contamination value ( Δ C ¯ C O 2 _ c r o s s _ A V ) was 63.9 ppm. The average value of the CO2 concentration in the exhaust inlet section of the heat wheel ( C ¯ C O 2 _ H W E _ A V ) was 390.1 ppm. Based on the results, the relative average of CO2 cross-contamination ( Δ C ¯ C O 2 _ R E L ) was 16.4% and the maximum value ( C C O 2 _ R E L _ M A X ) was recorded as 30.1%, considering the whole cooling season. To determine how the obtained values influence the indoor air quality inside of the conditioned spaces, further indoor air quality measurements are necessary (with the use of further measurement devices and questionnaires), which can act as a continuation of this research work, but exceed the limitation of this recent ongoing research project.

5. Conclusions

In this research work, a field study was carried out on the cooling energy performance of an existing, operating ventilation system under the operation of an air-to-air rotary heat wheel and direct expansion cooling coil, connected to a variable refrigerant volume outdoor unit. The major findings obtained from the study can be summarized as follows:
1. The operation of the heat wheel has a significant cooling energy saving impact on the electric energy consumption of the outdoor unit. Comparing the measured ventilation system with an air handling unit without a heat wheel operation, the cooling energy consumption is 25.1% higher;
2. Based on the measurements, the real sensible effectiveness and the CO2 cross-contamination of the heat wheel are not in accordance with the design assumptions for the cooling period;
3. The sensible effectiveness of the heat wheel performed 4.7% higher than the data (74.9%) given in the technical data book of the producer;
4. Having completed the measurements for the whole cooling period, the amount of CO2 cross-contamination in the heat wheel was much higher (with 16.4% relative average and 30.1% maximum values) than predicted during the designing phase.
Future work will focus on heating and annual energy performance investigations by conducting further field studies on the system. Moreover, simulation model development will also be considered for an annual energy consumption investigation of the existing ventilation system and model validation is planned based on data given by an annual field study. The long-term goal is to develop a simulation model which is suitable for determination of the energy consumption of ventilation systems in the design phase with a high accuracy.

Funding

The sensors, instruments, and transducers were financially supported and installed, and BMS software for data recording was made for this research work, by the national Intherm Ltd. In addition, the research project was financially supported by the National Research, Development and Innovation Office from the NRDI Fund [grant number: NKFIH PD_18 127907], the János Bolyai Research Scholarship of the Hungarian Academy of Sciences, Budapest, Hungary. Moreover, the research reported in this paper has been supported by the National Research, Development and Innovation Fund (TUDFO/51757/2019-ITM, Thematic Excellence Program), as well as the Higher Education Excellence Program of the Ministry of Human Capacities in the frame of Artificial Intelligence research area of Budapest University of Technology and Economics (BME FIKP-MI).

Acknowledgments

The author wishes to thank Árpád Nagy and Gyula Szabó from the group of Intherm Ltd., as well as Balázs Zuggó and Noémi Bálint from the group of Daikin Hungary Ltd., for providing their professional technical and practical knowledge for the research background of this research. Moreover, special thanks go to Laith Al-Hyari for his contribution in simple data saving.

Conflicts of Interest

The author declares no conflicts of interest.

Nomenclature

Abbreviations
AConstant value (-)
AHUAir Handling Unit (-)
CO2Carbon dioxide (ppm)
cpaSpecific heat of air at constant pressure (kJ/(kg·°C))
cpwSpecific heat of water vapor at constant pressure (kJ/(kg·°C))
EEREnergy efficiency ratio (-)
hEnthalpy (kJ/kg)
mConstant value (-)
m ˙ Air mass flow rate (kg/h)
PPressure (Pa); electric energy consumption of the outdoor unit (kWh)
RHRelative humidity (%)
tTemperature (°C)
tnConstant value (-)
VRVVariable refrigerant volume (-)
V ˙ Air volume flow rate (m3/h)
xAbsolute humidity (gwater/kgdry air)
Greek Letters
ƐsSensible effectiveness (-)
τ Time (hr)
Subscripts
DXSupply outlet section direct expansion evaporator
EIExhaust air inlet
HWEExhaust inlet section of the heat wheel
HWSSupply outlet section of the heat wheel
OOutdoor
sSaturation
SISupply air inlet
SOSupply air outlet
wWater vapor

References

  1. Zhong, C.; Yan, K.; Dai, Y.; Jin, N.; Lou, B. Energy Efficiency Solutions for Buildings: Automated Fault Diagnosis of Air Handling Units Using Generative Adversarial Networks. Energies 2019, 12, 527. [Google Scholar] [CrossRef]
  2. Misevičiūtė, V.; Valančius, K.; Motuzienė, V.; Rynkun, G. Analysis of exergy demand for air heating of an air handling unit. Energy Effic. 2017, 10, 989–998. [Google Scholar]
  3. Cui, X.; Mohan, B.; Islam, M.R.; Chua, K.J. Investigating the energy performance of an air treatment incorporated cooling system for hot and humid climate. Energy Build. 2017, 151, 217–227. [Google Scholar] [CrossRef]
  4. Ukai, M.; Tanaka, H.; Tanaka, H.; Okumiya, M. Performance analysis and evaluation of desiccant air-handling unit under various operation condition through measurement and simulation in hot and humid climate. Energy Build. 2018, 172, 478–492. [Google Scholar] [CrossRef]
  5. Shea, R.P.; Kissock, K.; Selvacanabady, A. Reducing university air handling unit energy usage through controls-based energy efficiency measures. Energy Build. 2019, 194, 105–112. [Google Scholar] [CrossRef]
  6. Kusiak, A.; Zeng, Y.; Xu, G. Minimizing energy consumption of an air handling unit with a computational intelligence approach. Energy Build. 2013, 60, 355–363. [Google Scholar] [CrossRef]
  7. Guo, Y.; Zhang, G.; Zhou, J.; Wu, J.; Shen, W. A techno-economic comparison of a direct expansion ground-source and a secondary loop ground-coupled heat pump system for cooling in a residential building. Appl. Therm. Eng. 2012, 35, 29–39. [Google Scholar] [CrossRef]
  8. Jorissen, F.; Boydens, W.; Helsen, L. Validated air handling unit model using indirect evaporative cooling. J. Build. Perform. Simul. 2018, 11, 48–64. [Google Scholar] [CrossRef]
  9. Wallin, J.; Claesson, J. Improving heat recovery using retrofitted heat pump in air handling unit with energy wheel. Appl. Therm. Eng. 2014, 62, 823–829. [Google Scholar] [CrossRef]
  10. Yun, G.Y.; Choi, J.; Kim, J.T. Energy performance of direct expansion air handling unit in office buildings. Energy Build. 2014, 77, 425–431. [Google Scholar] [CrossRef]
  11. Ukai, M.; Okumiya, M. Comparison of Behaviour and Energy Performance of Desiccant Air Handling Unit under Various Control Method. In IOP Conference Series: Earth and Environmental Science, Proceedings of the 4th Asia Conference of International Building Performance Simulation Association (ASIM2018), Hong Kong, China, 3–5 December 2018; IOP Publishing: Bristol, UK, 2019; Volume 238, p. 012027. [Google Scholar]
  12. Angrisani, G.; Roselli, C.; Sasso, M.; Tariello, F. Dynamic performance assessment of a solar-assisted desiccant-based air handling unit in two Italian cities. Energy Convers. Manag. 2016, 113, 331–345. [Google Scholar] [CrossRef]
  13. Kim, S.H.; Moon, H.J. Case study of an advanced integrated comfort control algorithm with cooling, ventilation, and humidification systems based on occupancy status. Build. Environ. 2018, 133, 246–264. [Google Scholar] [CrossRef]
  14. Li, N.; Xia, L.; Shiming, D.; Xu, X.; Chan, M. Dynamic modeling and control of a direct expansion air conditioning system using artificial neural network. Appl. Energy 2012, 91, 290–300. [Google Scholar] [CrossRef]
  15. Stamatescu, G.; Stamatescu, I.; Arghira, N.; Fagarasan, I. Data-Driven Modelling of Smart Building Ventilation Subsystem. J. Sens. 2019, 2019, 3572019. [Google Scholar] [CrossRef]
  16. Hong, G.; Kim, B.S. Development of a Data-Driven Predictive Model of Supply Air Temperature in an Air-Handling Unit for Conserving Energy. Energies 2018, 11, 407. [Google Scholar] [CrossRef]
  17. Noussan, M.; Carioni, G.; Degiorgis, L.; Jarre, M.; Tronville, P. Operational performance of an Air Handling Unit: Insights from a data analysis. Energy Procedia 2017, 134, 386–393. [Google Scholar] [CrossRef]
  18. Bareschino, P.; Pepe, F.; Roselli, C.; Sasso, M.; Tariello, F. Desiccant-Based Air Handling Unit Alternatively Equipped with Three Hygroscopic Materials and Driven by Solar Energy. Energies 2019, 12, 1543. [Google Scholar] [CrossRef]
  19. Daikin Ventilation Catalogue. Daikin Europe Naamloze Vennootschap, Zandvoordestraat 300, 8400 Oostende, Belgium, RPR Oostende. 2019. Available online: https://www.daikin.eu/content/dam/document-library/catalogues/Ventilation%20catalogue%20-%20ECPEN13-203_Catalogues_English.pdf (accessed on 8 August 2019).
  20. Oyj, V. Vaisala, Humidity Conversion Formulas. Helsinki, Finland. 2013. Available online: https://www.hatchability.com/Vaisala.pdf (accessed on 8 November 2019).
  21. Rajput, R.K. Thermal Engineering, 6th ed.; Firewall/Laxmi Publications Ltd.: New Delhi, India, 2006; ISBN 81-7008-834-8. [Google Scholar]
  22. European Committee for Standardization. Ventilation for Buildings—Performance Testing of Components/Products for Residential Ventilation—Part 7: Performance Testing of Components/Products of Mechanical Supply and Exhaust Ventilation Units (Including Heat Recovery) for Mechanical Ventilation Systems Intended for Single Family Dwellings; EN 13141-7:2010; CEN: Brussels, Belgium, 2010. [Google Scholar]
  23. American Society of Heating. Method of Testing Air-To-Air Heat Exchangers, ASHRAE Standard 84-1991; American Society of Heating, Refrigerating and Air Conditioning Engineers Inc.: Atlanta, GA, USA, 1991. [Google Scholar]
Figure 1. Photo from the investigated air handling units (AHU).
Figure 1. Photo from the investigated air handling units (AHU).
Energies 12 04267 g001
Figure 2. Photo from the outdoor unit.
Figure 2. Photo from the outdoor unit.
Energies 12 04267 g002
Figure 3. Schematic diagram (a) for the placement of the measurement points on the real operating AHU and (b) the AHU without a heat recovery operation assumption.
Figure 3. Schematic diagram (a) for the placement of the measurement points on the real operating AHU and (b) the AHU without a heat recovery operation assumption.
Energies 12 04267 g003
Figure 4. A screenshot of the investigated AHU in the Building Management System (BMS).
Figure 4. A screenshot of the investigated AHU in the Building Management System (BMS).
Energies 12 04267 g004
Figure 5. The air temperature values in the air handling processes.
Figure 5. The air temperature values in the air handling processes.
Energies 12 04267 g005
Figure 6. The air relative humidity values in the air handling processes.
Figure 6. The air relative humidity values in the air handling processes.
Energies 12 04267 g006
Figure 7. The air enthalpy values in the air handling processes.
Figure 7. The air enthalpy values in the air handling processes.
Energies 12 04267 g007
Figure 8. The sensible effectiveness values as a function of outdoor air temperature in June.
Figure 8. The sensible effectiveness values as a function of outdoor air temperature in June.
Energies 12 04267 g008
Figure 9. The energy recovery and auxiliary cooling energy consumption for ventilation.
Figure 9. The energy recovery and auxiliary cooling energy consumption for ventilation.
Energies 12 04267 g009
Figure 10. The electric energy consumption of the outdoor unit.
Figure 10. The electric energy consumption of the outdoor unit.
Energies 12 04267 g010
Figure 11. The carbon dioxide values in the investigated supply and exhaust sections of the heat wheel.
Figure 11. The carbon dioxide values in the investigated supply and exhaust sections of the heat wheel.
Energies 12 04267 g011
Table 1. Specification of the investigated AHU [19].
Table 1. Specification of the investigated AHU [19].
ParameterValueUnit
Width × Height × Length1450 × 1340 × 2897mm
Air flow1060m3/h
External Pressure Drop 280Pa
Weight595kg
Table 2. Technical data of the outdoor unit [19].
Table 2. Technical data of the outdoor unit [19].
ParameterValueUnit
Total Cooling Capacity10.9kW
RefrigerantR410a-
EER3.99-
Fin MaterialAluminium-
Tube MaterialCopper-
Table 3. Specification of the investigated heat wheel [19].
Table 3. Specification of the investigated heat wheel [19].
ParameterValueUnit
Heat recovered 2kW
Effectiveness74.9%
Diameter600mm
Table 4. Specification of the sensors and instrument.
Table 4. Specification of the sensors and instrument.
ModelDeviceWorking RangeAccuracy
Honeywell VF20-3B65NW Temperature sensor−40–150 °C±0.4 °C
Honeywell LFH20-2B65Humidity sensor10–90%±3%
Honeywell AQS-KAM-20CO2 sensor0–2000 ppm±50 ppm
Honeywell AV-D-10Air velocity sensor2–20 m/s±0.2 m/s
Inepro Metering Pro 380Electricity energy meter5–100 A±1%

Share and Cite

MDPI and ACS Style

Kassai, M. Energy Performance Investigation of a Direct Expansion Ventilation Cooling System with a Heat Wheel. Energies 2019, 12, 4267. https://doi.org/10.3390/en12224267

AMA Style