Article

Experimental Characterization, Modeling, and Numerical Evaluation of a Novel Friction Damper for the Seismic Upgrade of Existing Buildings

Department of Architecture, Built Environment and Construction Engineering, Politecnico di Milano, Piazza Leonardo da Vinci 32, 20133 Milan, Italy
*
Author to whom correspondence should be addressed.
Materials 2023, 16(5), 1933; https://doi.org/10.3390/ma16051933
Submission received: 7 February 2023 / Revised: 16 February 2023 / Accepted: 24 February 2023 / Published: 26 February 2023

Abstract

:
The paper presents the experimental characterization, the formulation of a numerical model, and the evaluation, by means of non-linear analyses, of a new friction damper conceived for the seismic upgrade of existing building frames. The damper dissipates seismic energy through the friction force triggered between a steel shaft and a lead core prestressed within a rigid steel chamber. The friction force is adjusted by controlling the prestress of the core, allowing the achievement of high forces with small dimensions, and reducing the architectural invasiveness of the device. The damper has no mechanical parts subjected to cyclic strain above their yield limit, thereby avoiding any risk of low-cycle fatigue. The constitutive behavior of the damper was assessed experimentally, demonstrating a rectangular hysteresis loop with an equivalent damping ratio of more than 55%, a stable behavior over repeated cycles, and a low dependency of the axial force on the rate of displacement. A numerical model of the damper was formulated in the OpenSees software by means of a rheological model comprising an in-parallel system of a non-linear spring element and a Maxwell element, and the model was calibrated on the experimental data. To assess the viability of the damper for the seismic rehabilitation of buildings, a numerical investigation was conducted by performing non-linear dynamic analyses on two case-study structures. The results highlight the benefits of the PS-LED in dissipating the largest part of seismic energy, limiting the lateral deformation of the frames, and controlling the increase in structural accelerations and internal forces at the same time.

1. Introduction

The implementation of energy dissipation devices inside structural frames has proven to be an effective technique for improving the seismic behavior of existing constructions [1,2,3,4,5,6,7,8,9,10]. Generally speaking, energy dissipation devices can be categorized into two families, namely fluid viscous dampers, which response depends on the rate of deformation, and hysteretic dampers, which response mainly depends on the magnitude of deformation [11]. While fluid viscous dampers are more popular for strategic structures (such as hospitals, police stations, and fire stations) and high-rise buildings [12,13,14,15,16,17,18,19,20,21], hysteretic dampers are generally used for the retrofit of ordinary buildings, as demonstrated in numerous studies [22,23,24,25,26]. In framed structures, energy dissipation devices are usually incorporated within steel braces installed between consecutive floors [11], which permits the activation of the dampers by exploiting the relative displacement between the stories. The combination of steel braces and energy dissipation devices is beneficial since the braces provide an increase in structural stiffness that reduces structural displacement, while the dampers, through the dissipation of seismic energy, dampen vibrations and reduce structural acceleration [10,27,28,29]. However, the installation of damped braces in existing structures requires an important amount of construction work, resulting in significant disturbances for occupants and critical alterations to the building layout because of their excessive dimensions, which ruin the esthetic and architecture of buildings [30].
Another important drawback of damped braces is the increase in internal forces in the structural elements that surround these dissipative systems, which often need local strengthening, especially at connections that are particularly sensitive to stress concentration [2,7,31,32]. Moreover, the stiffening effect of these braces decreases the vibration period of structures, causing an increase in horizontal forces at the foundation level [30]. This requires further expensive interventions to strengthen the foundations of the main frame [7,30,31,32,33].
Among the various types of current hysteretic dampers [24,29,30,31,32,33,34,35,36], buckling-restrained braces (BRBs) are perhaps the most popular system and are used for both new and retrofitted structures [2,37,38,39]. BRBs dissipate seismic energy through the inelastic deformation of a mild steel core confined in a rigid metal sleeve, which provides buckling resistance and allows the development of large and stable hysteretic loops with an almost symmetric hysteretic behavior [37,38,40,41,42,43], providing an equivalent damping ratio on the order of 20% to 40%. Due to their widespread use, modern codes for seismic retrofit (e.g., ASCE 41-17 [44]) and seismic design (e.g., AISC 341-16 [45], ASCE 7–16 [46]) have incorporated general guidelines for the design of BRB frames. However, BRBs are susceptible to low-cycle fatigue failure due to their limited cumulative ductility capacity [47,48,49,50,51,52], which limits their survivability in case of long-duration or repeated seismic sequences, possibly leaving a structure unprotected in the case of, e.g., main shock–aftershock sequences.
Some authors of this paper have recently proposed a novel damper, named the PreStressed-Lead Damper (PS-LED), which dissipates seismic energy through the friction force triggered between a moving shaft and a lead core [3,4,5]. Because of an essentially rectangular hysteretic cycle, the damper is expected to provide an equivalent damping ratio close to 60%. Moreover, since there are no mechanical parts subjected to inelastic deformation, this device is insensitive to low-cycle fatigue, and, therefore, it can survive multiple design earthquakes.
In the present study, the PS-LED was characterized following the recommendations of the European standard EN 15129 [53], which is compulsory in Europe for the CE Marking of anti-seismic devices, and its viability for the seismic retrofit of existing structures was investigated via numerical analyses. In particular, Section 2 reports the results of an experimental campaign on a prototype of the PS-LED and the formulation of a numerical model aimed at representing the constitutive behavior of the device in the OpenSees software program [54,55]. In Section 3, two structures, including a reinforced concrete (RC) residential building and a steel moment-resisting framed (MRF) office building, are taken as the case studies and retrofitted by means of Chevron braces equipped with the PS-LED. The seismic upgrade of the two buildings is performed at the ultimate limit state in compliance with the Italian Building Code (NTC-18) [56], and the effectiveness of the damper is assessed by means of non-linear analyses.

2. Characterization and Modeling of the PS-LED

2.1. Description of the Device

The PS-LED consists of a steel sleeve filled with lead, in which a steel shaft slides due to the effect of an external action, as shown in Figure 1. The linear motion of the shaft is driven by a bushing in the cap, which also prevents the leakage of lead. Spherical joints are provided at either end of the damper to prevent the transmission of bending moments.
The lead core is prestressed after the assembling of the damper in order to remove voids formed during the casting process, resulting in a perfect fit to the sleeve and the shaft [1,3]. During the sliding of the shaft, the force F0 of the PS-LED is expressed by the formula of Equation (1):
F 0 = μ k × p × A
where μk is the coefficient of friction at the interface between the shaft and the lead core; p is the contact stress at the interface; and A is the area of the lateral surface of the shaft sliding within the lead core. Prestressing the lead core increases the contact stress p, and hence the force of the damper, permitting the achievement of high strength combined with small dimensions of the device. Previous numerical simulations have demonstrated [3] that the force F0 of the PS-LED increases almost proportionally with the axial strain of the lead core ε until a certain strain level is reached, corresponding to the yielding of the lead core, and beyond which no further increase occurs, as shown in Figure 2.

2.2. Experimental Campaign

A prototype of the PS-LED, which was rated for a nominal force of 220 kN and a seismic displacement dbd of 20 mm in either direction, was tested at the Materials Testing Laboratory of Politecnico di Milano, using a servohydraulic testing machine (MTS Systems, Eden Prairie, MN, USA) with a load capacity of 500 kN, as shown in Figure 3a.
The diameter of the shaft was Ds = 32 mm, the external diameter of the lead core was DL = 60 mm, and the length of the lead core was L = 80 mm. The materials were S355 carbon steel for the sleeve, 42CrMo4 steel for the shaft, and 99.99% pure lead for the core.
The typical experimental force–displacement curve of the PS-LED, as reported in Figure 3b, presents a linear initial branch, which corresponds to the elastic deformation of the shaft before sliding at the lead–shaft interface is triggered, followed by a zero-stiffness secondary branch corresponding to the sliding, with a constant friction, of the shaft within the core. The hysteresis loop is almost rectangular in shape, which maximizes energy dissipation for a given displacement amplitude. The damper force remains almost constant regardless of the accommodated displacement, indicating that the PS-LED is able to limit the stress increase in the structural frame in case the design displacement is exceeded during a strong earthquake.
The prototype of the PS-LED was subjected to the test protocol presented in Table 1. The Cyclic and the Ramp tests were performed in accordance with the provisions of the European standard EN 15129 [53]. The standard prescribes assessing damper properties by performing five sinusoidal cycles at both 25% and 50% of dbd, and ten cycles at dbd at the reference frequency of 0.5 Hz, corresponding to a period of a structural system in which the tested device has to be used for 2 s. Then, the prototype was subjected to a monotonic ramp with increasing deformation up to the amplified displacement γb γx dbd, when the amplification factor γb and the reliability factor γx were equal to 1.1 and 1.2, respectively.
The Dynamic tests D1, D2, and D3, were performed to evaluate the dependence of the response of the PS-LED on velocity and consisted of five harmonic cycles, each at dbd, while considering a ±50% variation in frequency with respect to the reference value of 0.5 Hz (Table 1).
Eventually, three tests, S1, S2, and S3, though not requested by the standard [53], were carried out with the aim of assessing the survivability of the damper during repeated sequences of the design earthquake. In these tests, the PS-LED was subjected to three sequences of ten cycles each of sinusoidal displacement at the design seismic displacement dbd, with a dwell period of about 1 h between two consecutive sequences.
From the experimental load–displacement curves, the effective stiffness Keff and the equivalent damping ratio ξeff of the PS-LED were evaluated at each cycle according to Equations (2) and (3):
K eff = F d d
ξ eff = 2 π EDC 4   d   F d
where EDC is the energy dissipated per cycle; Fd is the maximum damper force in the cycle (averaged between the positive and negative branches); and d is the displacement amplitude.
According to the standard [53], the design properties of hysteretic dampers are determined at the third cycle of test C3. For the prototype under examination, the evaluated values were K eff = 22.3 kN/mm and ξeff = 55%. In this respect, it is worth recalling that the equivalent damping ratio of conventional BRBs generally does not exceed 40%.
The stability of the stiffness and damping properties of the PS-LED prototype in the Cyclic tests were checked in accordance with the standard [53], which prescribes a maximum change of ±10% in Keff and ξeff with respect to the values evaluated at the third cycle performed at the same amplitude (but disregarding the first cycle). The results reported in Table 2 show that the requirement was fulfilled.
The force–displacement curve assessed in the Ramp test for the amplified displacement γb γx dbd is shown in Figure 4. The prototype sustains the amplified displacement without any cracking, and after the peak in force in correspondence with the breakaway friction, the force–displacement curve presents a non-decreasing behavior.
The response of the PS-LED was found to exhibit a shallow dependency on velocity, as demonstrated in the Dynamic tests and shown in Table 3. The damper force, and consequently the effective stiffness, has a maximum variation of 4% over a variation in the frequency of +/− 50% with respect to the central frequency of f = 0.5 Hz, while the corresponding change in the equivalent damping ratio is about 3%.
Figure 5 illustrates the variation in the effective stiffness Keff and the equivalent damping ratio ξeff at each cycle of the tests S1, S2, and S3. Disregarding the first cycle of each sequence as recommended in the standard [53], the mechanical properties remained practically unchanged during the tests, with a maximum variation in Keff and ξeff, with respect to the values assessed at the third cycle of S1, of +7.3% and −2.6%, respectively. Eventually, it must be reported that, by adding up all the cycles performed in the experimental program (Table 1), the PS-LED prototype sustained a total of 55 cycles at the design seismic displacement without a deterioration of its properties, demonstrating the absence of low-cycle fatigue effects.

2.3. Modeling of the PS-LED in OpenSees

A rheological model of the PS-LED, named EPPV model [7,29,57], was formulated in the OpenSees framework [54,55] to perform non-linear dynamic analyses. This model is preferred over the velocity-dependent friction models that are already implemented in OpenSees since it allows a direct estimation of the relevant parameters from the Cyclic tests performed for the qualification of the damper according to the standard EN 15129 [53], without requiring additional experimental burden [7]. By referring to the hysteretic cycle produced by a sinusoidal input motion as shown in Figure 3b, the damper shows an almost elastic-perfectly plastic behavior, with “rounded” corners at the motion reversals, where the velocity is close to zero. These variations are due to the shallow dependence of the damper force on the rate of displacement, as confirmed by the Dynamic tests reported in Section 2.2. To describe such behavior, an in-parallel model was formulated (Figure 6), which includes an elastic-perfectly plastic material and a viscous Maxwell material. In particular, the contribution of the elastic-perfectly plastic material is identified with the force F1, while F2 is the force of the Maxwell material.
The EPPV model was coded in OpenSees [54,55] by using a zeroLength element [55] associated with a Parallel material, which includes two material objects, the uniaxialMaterial ElasticPP [55] and the uniaxialMaterial ViscousDamper [55,58]. This model is defined by 5 parameters: the yield displacement d y ; the plastic force V E P P of the uniaxialMaterial ElasticPP material object; the stiffness K d ; the damping coefficient C d ; and the velocity exponent α d of the uniaxialMaterial ViscousDamper material object.
By referring again to the hysteretic cycle shown in Figure 3b, the model parameters for the tested damper are determined as follows:
(i)
VEPP, which corresponds to the maximum force F1 of the uniaxialMaterial ElasticPP, is defined as a fixed share β of the maximum damper force Fd. Then, F2 is simply (1 − β)·Fmax.
(ii)
dy is defined on the initial branch of the force–displacement curve as the displacement at which VEPP is reached first.
(iii)
Kd is set equal to 100·(VEPP/dy), in order to concentrate the whole deflection of the Maxwell element in the dashpot.
(iv)
Cd is defined as the ratio F2/(vmax)αd, where vmax is the maximum velocity in the cycle and αd is the velocity exponent, which value is determined by minimizing the difference between the areas of the experimental and the analytical loops.
Figure 7 reports the model parameters identified for the investigated prototype of the PS-LED and shows the fair agreement between the experimental curve and the analytical model. The largest discrepancy between the two curves occurs in the first quadrant of the diagram, where the damper does not reach its maximum force due the inertia of the testing machine at the breakaway. The maximum force in tension and compression and the effective stiffness deviate by less than 1% between the model and the experiment, while for the EDC, the difference is on the order of 3% if considering the whole cycle, and less than 1% if ignoring the first quadrant.

3. Assessment of the PS-LED for the Retrofit of Existing Structures

3.1. Description of the Case-Study Buildings

Two existing frame structures taken from the literature [9,59] were assumed as the case studies, namely a residential RC building and a steel office building. These structures were chosen since they had been designed according to outdated codes, and they are characterized by some deficiencies in structural design that can be considered typical in existing structures.
The RC building is a 4-story structure located in the municipality of Potenza (Italy), which corresponds to a medium/high seismic area according to the classification of NTC-18 [56]. The elevation and plan view of the building, with the relevant main dimensions, are illustrated in Figure 8. The column and beam longitudinal reinforcements are shown in Figure 9; concerning the transversal reinforcement, the columns have φ6 stirrups spaced at 15 cm, whereas the beams have φ6 stirrups spaced at 15 cm at the end sections and at 20 cm elsewhere. The compressive strength of concrete is 20 MPa, and the yield strength of steel is 375 MPa; additional information can be found in reference [9]. The building was designed in the 1980s by considering vertical loads only and disregarding the effect of earthquake. Only the collapse of the case-study structure in bending is considered, while other possible failure mechanisms, e.g., shear failure of beams, columns or beam–column joints, bond slip, and low-cycle fatigue, which are rather common for old-code buildings [31], are not considered in the present work.
The steel MRF building [59,60,61] is shown in Figure 10, where the section and the length of the structural elements are reported. The peculiarity of this building consists of presenting different stiffnesses and strength capacities in the two main horizontal directions, due to the preferred orientation of the column sections, with their strong direction aligned to the Z-axis. The beams and columns are made of S355 steel.

3.2. Modeling of the Case-Study Frames in OpenSees

Full 3D numerical models were formulated in the OpenSees framework [54,55]. Both buildings had fixed supports at the ground floor to simulate rigid foundations, and the floor slabs were modeled as rigid diaphragms. Seismic masses at each floor, evaluated in compliance with the Italian code NTC-18 [56], were concentrated at the master nodes. Dead and live loads, as provided in the relevant references [9,59], were uniformly applied to the beams according to the warping shown in Figure 8 and Figure 10. Following [62,63], the beams and columns were modeled using the forceBeamColumn element object [64], which is composed of two external sub-elements of length Lpl corresponding to the end regions where inelastic behavior can be triggered, and an internal sub-element characterized by a linear elastic behavior. A different Lpl length was assumed for either case-study structure, namely, Equation (4) for the RC building and Equation (5) for the steel MRF.
L p l = z 30 + 0.2 h + 0.11 d b f y f c
Equation (4) is equivalent to the provision of the Eurocode 8 [65], where z is the shear span of the structural element, h is the depth of the section, db is the diameter of the longitudinal rebar, fy is the yield strength of steel, and fc is the compressive strength of concrete. According to the norm [65], Equation (4) is valid when a well-detailed confinement model of concrete is assumed [62]. For this reason, for the concrete model, the uniaxial material Concrete04 [55], which is based on the model proposed by Popovics [66], was implemented. Each steel bar corresponds to a single fiber, which is associated with the uniaxial Giuffre–Menegotto–Pinto constitutive law [67], corresponding to the Steel02 material with isotropic strain hardening [68] coded in the OpenSees libraries. A strain hardening ratio b = 0.01 was assumed, and the parameters that control the transition from the elastic to the plastic branch were set as R0 = 18, CR1 = 0.925, and CR2 = 0.15 [55]. In order to account for concrete cracking in the internal elastic sub-element, an effective area moment of inertia I e q defined as 50% of the gross area moment of inertia I g was introduced, according to the provisions of the NTC-18 [56].
For the steel MRF, Equation (5) was used [69,70], where Lv is the shear length of the steel member:
L p l = 0.22   L v
Again, the Steel02 material model with isotropic strain hardening [68] was implemented, where the yield strength f y , the modulus of elasticity E s , and the strain hardening ratio b were assigned to be equal to 355 MPa, 210,000 MPa, and 0.01, respectively.
The design properties of the materials were evaluated without considering the confidence factors [56,65]. P-Delta effects were considered in the analyses, and while the infill panels were not modeled, their contribution was taken into account as additional energy dissipation; indeed, equivalent viscous damping ratios of 5% for the RC frame (as in references [7,71,72,73]) and of 3% for the steel MRF (as in references [61,74,75]) were assumed.
Finally, an “axial buffer”, modeled as a zeroLength element object [55] with zero stiffness in the axial direction and high stiffnesses in shear and bending, was introduced in the RC frame model between one end of each beam and the adjacent node, in order to eliminate the axial force fictitiously generated by the interaction between the fiber sections of the beam elements and the rigid diaphragm [76].

3.3. Design of Seismic Retrofit with Chevron Braces Equipped with the PS-LED

The seismic upgrade of the two structures was designed by referring to the seismic loads provided by the NTC-18 [56] for life-safety limit state (SLV). In particular, the RC structure was upgraded considering the seismic hazard associated with the municipality of Potenza (latitude 40.65°, longitude 15.81°), with PGA = 2.45 m/s2, soil type B, and topographic factor T1 for a building with a functional class cu = II and a nominal life Vn = 50; the retrofit of the steel MRF considered the seismic hazard for the municipality of Lamezia Terme (latitude 38.57°, longitude 16.18°), with PGA = 4.47 m/s2, soil type C, and topographic factor T1 for a building with a functional class cu = II and a nominal life Vn = 100.
The dampers were sized by applying the DDBD retrofit procedure developed by the authors of this work [61,71,72,73]. According to this procedure, both the main frame and the dissipative braces are replaced by equivalent single-degree-of-freedom (SDOF) models, each one characterized by a secant stiffness and an equivalent viscous damping; the parameters of the equivalent SDOF damped brace are, hence, defined in relation to a “performance point” with a target displacement d p , which is assigned on the basis of the allowable damage of the main frame. In the last step, the strength and stiffness of the damped braces are distributed at each floor according to a proportionality criterion, in order to constrain the retrofitted frame to follow the first mode displacement of the bare frame. Further details can be found in references [2,29,61,71,72,73].
Different performance requirements were assumed for the two buildings. For the RC structure, the retrofit target was to avoid inelastic deformation of the structure under the effect of the basic design earthquake. In particular, the target displacement d p was defined, in agreement with reference [77], as the ending point of the elastic part of the capacity curve, as shown in Figure 11a. This performance level corresponds to the Immediate Occupancy performance level, which guarantees that the structure is immediately accessible after a main earthquake, since the strength and the stiffness of the structural elements are not compromised. On the contrary, in the case of the steel MRF, a controlled inelastic deformation of the main frame was permitted, with activation of plastic hinges and limited reparable damage, corresponding to a ductility factor of µF = 1.5 in accordance with the figure assumed in previous studies [59], as shown in Figure 11b.
Figure 11 shows the capacity curves of the two case-study structures in the X-direction; the blue dots on the curves identify the ending point of the elastic part, while the red dots highlight the assumed performance point. For the sake of conciseness, the results in the Z-direction are not reported, but the target displacement is 0.045 m for the RC structure and 0.265 m for the steel MRF, respectively. The seismic analyses of the bare frames (not reported in this paper for brevity) highlighted that, due to the preferred orientation of the column sections with their strong axis aligned in the Z-direction, the steel MRF needed to be upgraded in the X-direction only; interested readers can refer to [61] for more details. On the other hand, the RC frame needed to be strengthened in both directions.
The two structures were retrofitted by means of Chevron (or reversed-V) steel braces with the PS-LED placed at the intersection of the two rods of the brace and connected to the midsection of the beam of the upper floor. Figure 12 and Figure 13 show the plan layout of the damped braces in both case-study buildings and the elevation layout of the braces in the RC structure, respectively.
For design, the PS-LED were modeled as elastic-perfectly plastic devices, as shown in Figure 14. The design properties of the model are the yield force F0, the elastic stiffness K1, and the ductility factor μD = du/dy. All other parameters of the ideal curve can be derived from these properties.
The steel braces were assigned to have a stiffness twice the PS-LED stiffness, as suggested, e.g., in [9], in order to guarantee that the largest part of the deformation of the story is concentrated in the damper, which enhances the amount of energy dissipation [78,79].
The properties of the dissipative braces are distributed at each story according to a proportionality criterion [80], which ensures that the first modal shape of the bare frame remains unvaried after the upgrade. This choice, which is justified by the vertical regularity of the buildings, avoids drastic changes to the internal action distribution in the frame, at least in the range of the elastic behavior. Moreover, the chosen distribution of strength of the dissipative braces aims at achieving simultaneous yielding of the devices at all the stories and, thus, a global ductility of the bracing system coinciding with the ductility of the single brace [81]. Table 4 and Table 5 report the values of F0 and K1 of the dampers at each floor of the RC structure and of the steel MRF, respectively, as evaluated from the design procedure assuming μD = 20, which corresponds to an equivalent viscous damping ratio ξeff = 55% (Figure 14).
It is worth mentioning that Table 4 and Table 5 list the design properties of the PS-LED units obtained from the sizing procedure. In a real application, at this step, the designer would choose from the portfolio of the manufacturer the devices that better match the design values, while also taking into consideration other practical issues, such as the need to use few sizes in order to reduce manufacturing costs [7]. However, for the scope of the present paper, the verification of the upgraded buildings was performed by referring to the design values listed in the above tables.

3.4. Seismic Performance and Evaluation of Retrofit Effectiveness

The effectiveness of the PS-LED for the seismic retrofit was investigated by means of bidirectional NLDAs, which were performed in compliance with the NTC-18 [56], considering seven pairs of artificial accelerograms generated by the computer program SIMQKE [82]. The accelerograms had a duration of the pseudo-stationary part of 10 s and a total duration of 25 s, and the mean 5% damping elastic spectrum calculated from all time histories was compatible with the target 5% damping elastic response spectrum defined by the code [56] in the range of periods between 0.15 and 2 s. Artificial accelerograms with a smooth spectrum were chosen as they allow a more accurate control of the frame response than real accelerograms, making the interpretation simpler and more focused on the specific aspects that were investigated in the analyses [7,71]. In the OpenSees models [54,55], the PS-LED was formulated as a concentrated zero-length element (zeroLength element object in the OpenSees framework [55]) with the associated EPPV rheological model presented in Section 2, while the steel braces were represented as truss elements with a perfectly elastic behavior (uniaxialMaterial Elastic [55]).
The benefits of introducing Chevron braces equipped with the PS-LED in the case-study structures are illustrated in Figure 15 and Figure 16, which show the maximum inter-story drift ratio Δ and the peak floor acceleration (PFA) at each story calculated by averaging the maxima of the results obtained for each pair of accelerograms. For the sake of brevity, the results reported in the Figures refer to the X-direction only, but the findings in the Z-direction for the RC frame are included in the discussion as well.
Figure 15 highlights the substantial reduction in Δ passing from the as-built frames to the retrofitted configurations, which is combined with a small decrement in PFA, due to the damping provided by the PS-LED (Figure 16). The upgraded structures show drift ratios that are more than 50% lower than those of the as-built frames, with a maximum decrease of −76.7% at the second floor of the RC frame and −66.6% at the first floor of the steel MRF, respectively. It is noted that with conventional dampers, the structural stiffening introduced by dissipative braces is normally accompanied by an increase in floor acceleration [23]. In contrast, with the PS-LED, due to the combined effects of stiffening provided by the braces, which decreases the vibration period by reducing displacements but increasing accelerations, and damping introduced by the PS-LED, which lowers the response spectra, it is possible to control the deformation of the building and the structural acceleration at the same time (Figure 17). The benefit of energy dissipation introduced by the PS-LED is also evident when looking at Figure 18, which shows the maximum shear force V at each floor. For both structures under the basic design earthquake, the retrofitted configurations exhibit a small increase in the base shear, which is on the order of 24.5% for the RC frame and of 5% only for the steel MRF. Therefore, the use of the PS-LED may reduce the need for invasive and expensive strengthening of the foundations, which is usually required when hysteretic steel dampers are used.
It is interesting to note in Figure 18 that for both buildings at the upper floors, the maximum shear force of the retrofitted frame is smaller than that of the as-built structure, but the opposite occurs at the lower floors. This behavior can be explained by noticing in Table 4 and Table 5 that the yield force of the PS-LED damper increases toward the lower floors. Specifically, at the fourth floor, the force of the PS-LED damper is about one third of the force of the device at the first floor. However, at each story, regardless of the damper force, the overall damping introduced in the building by the damped braced systems produces a consistent decrease in floor accelerations. For this reason, at the upper floors (third and fourth floors of the steel MRF, and fourth floor of the RC frame), the shear force of the retrofitted building is smaller than that of the as-built structure. On the contrary, at the lower floors, the force of the PS-LED overcomes the reduction in the inertia force due to the lower acceleration, resulting in a moderate increase in the total shear.
Figure 19 compares the maximum shear force in the most stressed column (corresponding to position C11 according to Figure 12a) at every floor of the RC frame. The introduction of the dissipation braces produces a substantial decrease in the shear force at each story; for example, at the ground floor, where the largest value is attained, the force passes from 50.3 kN in the as-built configuration to 36.4 kN in the upgraded configuration. This effect is ascribed to the Chevron braces, which create an alternative channel for the horizontal forces, reducing the amount of shear force transmitted through the columns. However, the vertical component of the force through the inclined braces is transferred to the columns of the lower floors, which are therefore subjected to a higher axial force. The columns at the ground floor of the RC structure were checked in the moment–axial load (M–N) interaction diagram. Figure 20 reports the results for the element at position C11. As shown in the panels, the check is not verified in the as-built configuration, and the column is expected to collapse in flexure. In contrast, the introduction of the dissipative braces causes both a reduction in the bending moment (related to the reduction in shear force) and an increase in the axial force, which globally provide a fulfillment of the resistance check.
On the other hand, a typical issue for steel frames is represented by the buckling of slender columns. The relevant check was, therefore, performed in order to evaluate the effect of an increased compressive force on the columns of the retrofitted steel structure. The results for the most stressed column (corresponding to position C14 according to Figure 12b) are shown in Figure 21, where the maximum axial force of the column at each floor is compared to the relevant buckling load (Nbuckling) calculated according to the NTC-18 [56]. Despite a non-negligible increase in the axial force (at the ground level, the axial load rises from 1035.3 kN to 1549.0 kN), the check is verified.
In order to highlight the contribution of energy dissipation provided by the PS-LED, the energy time histories of the frame and of the dampers are evaluated. In particular, the absolute input energy [83] is determined at each floor according to the expression of Equation (6):
E I j = 0 t m j ϋ t j d υ g
where the index “j” refers to the jth story, and the relevant parameters are mj, the mass associated with the jth story; ϋtj, the absolute acceleration of the jth story; and υg, the ground displacement.
In Figure 22, the absolute input energy introduced by the most demanding input accelerogram is compared with the energy dissipated by the PS-LED dampers installed in the perimetral frames in the X-direction of the upgraded structures. The energy dissipated by the PS-LED is calculated as the sum of the areas enclosed in the hysteretic cycles. As an example, the force–displacement cyclic behavior of the dampers installed at every floor of the steel MRF is reported in Figure 23. These loops highlight the excellent agreement between the actual strength of the dampers and the design values reported in Table 5, confirming the effectiveness of the proposed EPPV model. As shown in Figure 22, in the case of the RC structure, the dampers dissipate about 95% of the total input energy, while in the case of the steel MRF, the dissipated energy is about 92% of the input energy. By recalling that an equivalent viscous damping ratio of 5% was assumed for the RC frame, and a ratio of 3% was assumed for the steel MRF, these results are in fair agreement with the target of the retrofit design, which aimed at guaranteeing an essentially elastic behavior of the RC frame and permitting limited inelastic deformations of the steel frame. It is also worth noting that, for both structures, the input energies calculated in the as-built and retrofitted configurations are quite close to each other. However, in the as-built configuration, when disregarding the small contribution of the structural viscous damping, the input energy is totally dissipated through the inelastic deformation of the structural members, which therefore undergo severe damage.

4. Conclusions

The present work deals with a novel damper, named the PS-LED, which dissipates the input seismic energy through the friction force triggered between a steel shaft and a lead core prestressed within a rigid steel chamber. The friction force is adjusted by controlling the prestress of the core, allowing the achievement of high forces with small dimensions, which reduces the architectural invasiveness of the device. The damper was experimentally investigated, and a numerical model was coded in the OpenSees framework [54,55]. To assess the viability of the PS-LED for the seismic upgrade of existing buildings, a RC frame and a steel frame were considered as the case studies. Steel braces equipped with the PS-LED were designed to obtain a retrofitted structure that is able to withstand, at a specified performance level, the seismic demand associated with the life-safety limit state. Successively, the performance of the retrofitted buildings was evaluated by performing NLDAs under a set of artificial ground motion records. The main conclusions of the study are as follows:
(i)
The prototype of the PS-LED exhibits a stable response during repeated cycles performed at the design displacement, fulfilling the qualification requirements of the European standard [53] and providing an equivalent damping ratio on the order of 55%. Differently from current hysteretic dampers, such as buckling-restrained braces, the novel damper has no mechanical parts subjected to cyclic strain above their yield limit; therefore, the risk of low-cycle fatigue is avoided, and the device is expected to be able to withstand an unlimited number of cycles without deterioration or failure.
(ii)
A rheological model of the PS-LED was formulated in the OpenSees software program, consisting of an in-parallel arrangement of two material objects, namely an elastic-perfectly material (uniaxialMaterial ElasticPP) and a Maxwell model (uniaxialMaterial Viscous Damper). The model is able to reproduce the fundamental behavior of the damper, including the light dependency on velocity highlighted by the tests, and provides accurate predictions of maximum force, effective stiffness, and energy dissipation.
(iii)
In the application examples, the PS-LED dampers are shown to dissipate the largest part of the input energy introduced in the structure by the design earthquake, guaranteeing the protection of the main frame at the level specified by the design strategy (either elastic behavior or controlled inelastic deformation).
(iv)
A consequence of the excellent dissipative behavior of the PS-LED is the ability, in the examined case studies, to control the shear forces in the columns and foundations of the retrofitted frame; therefore, additional strengthening of the main structure may be not necessary or may be limited, resulting in a potential reduction in the total cost of the retrofit intervention.
Although the experimental investigation was restricted to a single size of the device, this study highlights the potential advantages of the PS-LED over current steel dampers for improving the survivability of structures to repeated ground motions, such as during the main shock–aftershock sequences, as well as reducing the need for local strengthening of the main frame. Future developments of the present work will concern the testing of prototypes with different yield forces and displacement capacities in order to evaluate the effect of the dimensions of the device on mechanical behavior, and to investigate experimentally the relationship between the prestress applied to the lead core and the strength of the PS-LED, with the aim of deriving design charts that can be used by manufacturers for the mechanical sizing of the device. Additionally, the performance of buildings reinforced with the PS-LED will be investigated while considering different seismic scenarios, such as those corresponding to service limit states and ultimate limit states.

Author Contributions

Conceptualization, V.Q.; methodology, V.Q. and E.B.; software, L.Z.; validation, V.Q., E.B. and S.C.; formal analysis, E.B.; writing—original draft preparation, E.B.; writing—review and editing, V.Q. and S.C. All authors have read and agreed to the published version of the manuscript.

Funding

This work was funded by the Italian Department of Civil Protection (DPC) in the framework of the national Research Project DPC-ReLUIS 2022-2024, Work Package WP 15 “Contributi normativi a isolamento e dissipazione”.

Data Availability Statement

The data presented in this study are available from the corresponding author upon request. The data are not publicly available as they are generated within a research project funded by the Italian Department of Civil Protection.

Acknowledgments

The authors are grateful to Giacomo Vazzana, Roberto Minerva, and the Materials Testing Laboratory of Politecnico di Milano for the support in the execution of the tests of the PS-LED prototype.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Quaglini, V.; Pettorruso, C.; Bruschi, E. Experimental and numerical assessment of prestressed lead extrusion dampers. Int. J. Eng. 2021, XXXVIII, 46–69. [Google Scholar]
  2. Quaglini, V.; Bruschi, E. Controllo passivo mediante controventi dissipativi. Principi generali, requisiti normativi ed evoluzione dei principali dispositivi a comportamento dipendente dallo spostamento. Structural 2022, 240, 9. [Google Scholar] [CrossRef]
  3. Quaglini, V.; Pettorruso, C.; Bruschi, E. Design and experimental assessment of a prestressed lead damper with straight shaft for seismic protection of structures. Geosciences 2022, 12, 182. [Google Scholar] [CrossRef]
  4. Quaglini, V.; Pettorruso, C.; Bruschi, E. Supplemental energy dissipation with prestressed Lead Extrusion Dampers (P-LED): Experiments and modeling. In Proceedings of the COMPDYN 2021, The 8th ECCOMAS Thematic Conference on Computational Methods in Structural Dynamics and Earthquake Engineering, Athens, Greece, 28–30 June 2021. [Google Scholar]
  5. Quaglini, V.; Bruschi, E.; Pettorruso, C.; Sartori, M. Design and experimental assessment of a novel damper with high endurance to seismic loads. Struct. Integr. Procedia 2023, 44, 1451–1457. [Google Scholar] [CrossRef]
  6. Di Cesare, A.; Ponzo, F.C.; Nigro, D. Assessment of the performance of hysteretic energy dissipation bracing systems. Bull. Earthq. Eng. 2014, 12, 2777–2796. [Google Scholar] [CrossRef]
  7. Bruschi, E.; Quaglini, V. Assessment of a novel hysteretic friction damper for the seismic retrofit of reinforced concrete frame structures. Structures 2022, 46, 793–811. [Google Scholar] [CrossRef]
  8. Quaglini, V.; Bruschi, E. Numerical investigation on the seismic performance of a RC framed building equipped with a novel Prestressed LEad Damper with Straight Shaft. Struct. Integr. Procedia 2023, 44, 1443–1450. [Google Scholar]
  9. Di Cesare, A.; Ponzo, F.C. Seismic retrofit of reinforced concrete frame buildings with hysteretic bracing systems: Design procedure and behaviour factor. Shock Vib. 2017, 2017, e2639361. [Google Scholar] [CrossRef] [Green Version]
  10. Freddi, F.; Ghosh, J.; Kotoky, N.; Raghunandan, M. Device uncertainty propagation in low-ductility RC frames retrofitted with BRBs for seismic risk mitigation. Earthq. Engng. Struct. Dyn. 2021, 50, 2488–2509. [Google Scholar] [CrossRef]
  11. Christopolous, C.; Filiatrault, A. Principles of Passive Supplemental Damping and Seismic Isolation; IUSS Press: Pavia, Italy, 2006. [Google Scholar]
  12. Ras, A.; Boumechra, N. Seismic energy dissipation study of linear fluid viscous dampers in steel structure design. Alex Eng. J. 2016, 55, 2821–2832. [Google Scholar] [CrossRef] [Green Version]
  13. Guo, T.; Xu, J.; Weijie, X.; Di, Z. Seismic upgrade of existing buildings with fluid viscous dampers: Design methodologies and case study. J. Perform. Constr. Facil. 2015, 29, 04014175. [Google Scholar] [CrossRef]
  14. Mokhtari, M.; Naderpour, H. Seismic vulnerability assessment of reinforced concrete buildings having nonlinear fluid viscous dampers. Bull. Earthq. Eng. 2022, 20, 7675–7704. [Google Scholar] [CrossRef]
  15. Miyamoto, K.; Gilani, A.S.J.; Glasgow, R.S. Seismic retrofit of a hospital building with supplementary damping devices. In Proceedings of the 2007 Structures Congress: New Horizons and Better Practices, Long Beach, CA, USA, 16–19 May 2007. [Google Scholar] [CrossRef]
  16. De Domenico, D.; Ricciardi, G.; Takewaki, I. Design strategies of viscous dampers for seismic protection of building structures: A review. Soil Dyn. Earthq. Eng. 2019, 118, 144–165. [Google Scholar] [CrossRef]
  17. De Domenico, D.; Hajirasouliha, I. Multi-level performance-based design optimisation of steel frames with nonlinear viscous dampers. Bull. Earthq. Eng. 2021, 19, 5015–5049. [Google Scholar] [CrossRef]
  18. Silvestri, S.; Gasparini, G.; Trombetti, T. A five-step procedure for the dimensioning of viscous dampers to be inserted in building structures. J. Earthq. Eng. 2010, 14, 417–447. [Google Scholar] [CrossRef]
  19. Palermo, M.; Muscio, S.; Silvestri, S.; Landi, L.; Trombetti, T. On the dimensioning of viscous dampers for the mitigation of the earthquake-induced effects in moment-resisting frame structures. Bull. Earthq. Eng. 2013, 11, 2429–2446. [Google Scholar] [CrossRef]
  20. Terenzi, G. Energy-Based Design criterion of dissipative bracing systems for the seismic retrofit of frame structures. Appl. Sci. 2018, 8, 268. [Google Scholar] [CrossRef] [Green Version]
  21. Sorace, S.; Terenzi, G. Seismic protection of framed structures by fluid viscous damped braces. J. Struct. Eng. 2008, 134, 45–55. [Google Scholar] [CrossRef]
  22. Aliakbari, F.; Garivani, S.; Aghakouchak, A.A. An energy based method for seismic design of frame structures equipped with metallic yielding dampers considering uniform inter-story drift concept. Eng. Struct. 2020, 205, 110114. [Google Scholar] [CrossRef]
  23. Gandelli, E.; Taras, A.; Disti, J.; Quaglini, V. Seismic retrofit of hospitals by means of hysteretic braces: Influence on acceleration-sensitive non-structural components. Front. Built. Env. 2019, 5, 100. [Google Scholar] [CrossRef]
  24. Gandelli, E.; Chernyshov, S.; Distl, J.; Dubini, P.; Weberd, F.; Taras, A. Novel adaptive hysteretic damper for enhanced seismic protection of braced buildings. Soil Dyn. Earthq. Eng. 2021, 141, 106522. [Google Scholar] [CrossRef]
  25. Garivani, S.; Askariani, S.S.; Aghakouchak, A.A. Seismic design of structures with yielding dampers based on drift demands. Structures 2020, 28, 1885–1899. [Google Scholar] [CrossRef]
  26. Golmoghany, M.Z.; Zahrai, S.M. Improving seismic behavior using a hybrid control system of friction damper and vertical shear panel in series. Structures 2021, 31, 369–379. [Google Scholar] [CrossRef]
  27. Bartera, F.; Giacchetti, R. Steel dissipating braces for upgrading existing building frames. J. Constr. Steel Res. 2004, 60, 751–769. [Google Scholar] [CrossRef]
  28. Yang, F.; Wang, G.; Li, M. Evaluation of the seismic retrofitting of mainshock-damaged reinforced concrete frame structure using steel braces with soft steel dampers. Appl. Sci. 2021, 11, 841. [Google Scholar] [CrossRef]
  29. Bruschi, E. Seismic Retrofit of RC Framed Buildings with Supplementary Energy Dissipation: Modelling and Application of a Novel Lead Damper. Ph.D. Thesis, Politecnico di Milano, Milan, Italy, 2021. [Google Scholar]
  30. Martínez-Rueda, J.E. On the evolution of energy dissipation devices for seismic de-sign. Earthq. Spectra 2002, 18, 309–346. [Google Scholar] [CrossRef]
  31. Ponzo, F.C.; Di Cesare, A.; Arleo, G.; Totaro, P. Protezione sismica di edifici esistenti con controventi dissipativi di tipo isteretico: Aspetti progettuali ed esecutivi. Progett. Sismica 2010, II, 19–42. [Google Scholar]
  32. Nuzzo, I.; Losanno, D.; Caterino, N. Seismic design and retrofit of frames structures with hysteretic dampers: A simplified displacement-based procedure. Bull. Earthq. Eng. 2019, 17, 2787–2819. [Google Scholar] [CrossRef]
  33. Sorace, S.; Terenzi, G. Existing prefab R/C industrial buildings: Seismic assessment and supplemental damping-based retrofit. Soil Dyn. Earthq. Eng. 2017, 94, 193–203. [Google Scholar] [CrossRef] [Green Version]
  34. Pall, A.S.; Marsh, C.; Fazio, P. Friction joints for seismic control of large panel structures. J. Prestress. Concr. Inst. 1980, 25, 38–61. [Google Scholar] [CrossRef]
  35. Pall, A.S.; Marsh, C. Response of friction damped braced frames. J. Struct. Div. 1981, 108, 1313–1323. [Google Scholar] [CrossRef]
  36. Palermo, M.; Silvestri, S.; Gasparini, G.; Trombetti, T. Crescent shaped braces for the seismic design of building structures. Mater. Struct. 2015, 48, 1485–1502. [Google Scholar] [CrossRef]
  37. Freddi, F.; Tubaldi, E.; Zona, A.; Dall’Asta, A. Seismic performance of dual systems coupling moment-resisting and buckling-restrained braced frames. Earthq. Engng. Struct. Dyn. 2021, 50, 329–353. [Google Scholar] [CrossRef]
  38. Gutiérrez-Urzúa, F.; Freddi, F. Influence of the design objectives on the seismic performance of steel moment resisting frames retrofitted with buckling restrained braces. Earthq. Engng Struct. Dyn. 2022, 51, 3131–3153. [Google Scholar] [CrossRef]
  39. Uang, C.M.; Nakashima, M.; Tsai, K.C. Research and application of buckling-restrained braced frames. Int. J. Steel Struct. 2004, 4, 301–313. [Google Scholar] [CrossRef]
  40. Zona, A.; Dall’Asta, A. Elasto-plastic model for steel buckling-restrained braces. J. Constr. Steel Res. 2012, 68, 118–125. [Google Scholar] [CrossRef]
  41. Gu, Q.; Zona, A.; Peng, Y.; Dall’Asta, A. Effect of buckling-restrained brace model parameters on seismic structural response. J. Constr. Steel Res. 2014, 98, 100–113. [Google Scholar] [CrossRef]
  42. Tremblay, R.; Poncet, L.; Bolduc, P.; Neville, R.; DeVall, R. Testing and design of buckling restrained braces for Canadian applications. In Proceedings of the 13th World Conference on Earthquake Engineering, Vancouver, Canada, 1–6 August 2004. [Google Scholar]
  43. Black, C.J.; Makris, N.; Aiken, I.D. Component testing, seismic evaluation and characterization of BRBs. J. Struct. Eng. 2002, 130, 880–894. [Google Scholar] [CrossRef]
  44. American Society of Civil Engineers. Seismic Evaluation and Retrofit of Existing Buildings; ASCE/SEI 41-17; American Society of Civil Engineers: Reston, VA, USA, 2017. [Google Scholar] [CrossRef] [Green Version]
  45. American Institute of Steel Construction. Seismic Provisions for Structural Steel Buildings; ANSI/AISC 341-16; American Institute of Steel Construction: Chicago, IL, USA, 2016. [Google Scholar]
  46. American Society of Civil Engineers. Minimum Design Loads and Associated Criteria for Buildings and Other Structures; ASCE/SEI 7-16; American Society of Civil Engineers: Reston, VA, USA, 2017. [Google Scholar] [CrossRef]
  47. Zona, A.; Ragni, L.; Dall’Asta, A. Sensitivity-based study of the influence of brace over-strength distributions on the seismic response of steel frames with BRBs. Eng. Struct. 2012, 37, 179–192. [Google Scholar] [CrossRef]
  48. Takeuchi, T.; Ida, M.; Yamada, S.; Suzuki, K. Estimation of cumulative deformation capacity of buckling restrained braces. J. Struct. Eng. 2008, 134, 822–831. [Google Scholar] [CrossRef]
  49. Andrews, B.M.; Fahnestock, L.A.; Song, J. Ductility capacity models for buckling-restrained braces. J. Constr. Steel Res. 2009, 65, 1712–1720. [Google Scholar] [CrossRef]
  50. Wei, X.; Ngeljaratan, L.; Bruneau, M. Low-cycle fatigue of Buckling Restrained Braces in bidirectional ductile end diaphragms due to temperature-change effect on bridge superstructure. J. Bridge Eng. 2019, 24, 04019014. [Google Scholar] [CrossRef] [Green Version]
  51. Li, C.H.; Vidmar, Z.; Saxey, B.; Reynolds, M.; Uang, C.M. A procedure for assessing low-cycle fatigue life of Buckling-Restrained Braces. J. Struct. Eng. 2022, 148, 04021259. [Google Scholar] [CrossRef]
  52. Tong, C.; Wu, J.; Hua, K.; Tian, H. Low-cycle fatigue life evaluation of buckling-restrained braces based on cumulative plastic deformation curves. Adv. Struct. Eng. 2022, 25, 336–354. [Google Scholar] [CrossRef]
  53. EN 15129; Anti-Seismic Devices. CEN (European Committee for Standardization): Brussels, Belgium, 2009.
  54. McKenna, F.; Fenves, G.I.; Scott, M.H. Open System for Earthquake Engineering Simulation; Pacific Earthquake Engineering Research Center: Berkeley, CA, USA, 2000. [Google Scholar]
  55. OpenSeesWiki Online Manual. Available online: https://opensees.berkeley.edu/wiki/index.php/Main_Page (accessed on 9 April 2022).
  56. Italian Council of Public Works. Technical Standards on Constructions; Italian Council of Public Works: Rome, Italy, 2018. (In Italian) [Google Scholar]
  57. Bruschi, E.; Quaglini, V. Modelling of a Novel Lead Damper and Application to an Existing RC Structure. In Proceedings of the Second Eurasian Conference on OpenSees, Turin, Italy, 7–8 July 2022. [Google Scholar]
  58. Akcelyan, S.; Lignos, D.G.; Hikino, T.; Nakashima, M. Evaluation of simplified and state-of-the-art analysis procedures for steel frame buildings equipped with supplemental damping devices based on E-Defense full-scale shake table tests. J. Struct. Eng. 2016, 142, 04016024. [Google Scholar] [CrossRef]
  59. De Domenico, D.; Gandelli, E.; Quaglini, V. Cyclic engagement of hysteretic steel dampers in braced buildings: A parametric in-vestigation. Bull. Earthq. Eng. 2021, 19, 5219–5251. [Google Scholar] [CrossRef]
  60. Vamvatsikos, D.; Bakalis, K.; Kohrangi, M.; Pyrza, S.; Castiglioni, C.A.; Kanyilmaz, A.; Morelli, F.; Stratan, A.; D’Aniello, M.; Calado, L.; et al. A risk-consistent approach to determine EN1998 behaviour factors for lateral load resisting systems. Soil Dyn. Earthq. Eng. 2020, 131, 106008. [Google Scholar] [CrossRef]
  61. Bruschi, E.; Quaglini, V.; Zoccolini, L. Control of the seismic response of steel-framed buildings by using supplementary energy dissipation devices. Appl. Sci. 2023, 13, 2063. [Google Scholar] [CrossRef]
  62. Bruschi, E.; Calvi, P.M.; Quaglini, V. Concentrated plasticity modelling of RC frames in time-history analyses. Eng. Struct. 2021, 243, 112716. [Google Scholar] [CrossRef]
  63. Bruschi, E.; Quaglini, V.; Calvi, P.M. Numerical assessment of concentrated plasticity models of ductile RC frames in non-linear dynamic analyses. In Proceedings of the 2nd fib Italy YMG Symposium on Concrete and Concrete Structures, Rome, Italy, 18–19 November 2021. [Google Scholar]
  64. Scott, M.H.; Fenves, G.L. Plastic Hinge Integration Methods for Force-Based Beam-Column Elements. J. Struct. Eng. 2006, 132, 244–252. [Google Scholar] [CrossRef]
  65. EN 1998–3 Eurocode 8; Design of Structures for Earthquake Resistance—Part 3: Assessment and Retrofitting of Buildings. CEN (European Committee for Standardization): Brussels, Belgium, 2005.
  66. Popovics, S. A numerical approach to the complete stress-strain curve of concrete. Cem. Concr. Res. 1973, 3, 583–599. [Google Scholar] [CrossRef]
  67. Menegotto, M.; Pinto, P.E. Method of analysis for cyclically loaded RC plane frames including changes in geometry and non-elastic behaviour of elements under combined normal force and bending. In Proceedings of the IABSE: Symposium on Resistance and Ultimate Deformability of Structures Acted on by Well Defined Repeated Loads, Lisboa, Portugal, 13–14 September 1973. [Google Scholar]
  68. Filippou, F.C.; Popov, E.P.; Bertero, V.V. Effects of Bond Deterioration on Hysteretic Behavior of Reinforced Concrete Joints, Report EERC 83-19 (1983); Earthquake Engineering Research Center, University of California: Berkeley, CA, USA, 1983. [Google Scholar]
  69. Bosco, M.; Tirca, L. Numerical simulation of steel I-shaped beams using a fiber-based damage accumulation model. Constr. Steel Res. 2017, 133, 241–255. [Google Scholar] [CrossRef]
  70. Barbagallo, F.; Bosco, M.; Ghersi, A.; Marino, E.M.; Rossi, P.P. Seismic assessment of steel MRFs by cyclic pushover analysis. Open Constr. Build. Tech. J. 2019, 13, 12–26. [Google Scholar] [CrossRef]
  71. Bruschi, E.; Quaglini, V.; Calvi, P.M. A simplified design procedure for seismic upgrade of frame structures equipped with hysteretic dampers. Eng. Struct. 2021, 251, e113504. [Google Scholar] [CrossRef]
  72. Quaglini, V.; Bruschi, E.; Pettorruso, C. Dimensionamento di dispositivi dissipativi per la riabilitazione sismica di strutture intelaiate. Structural 2021, 237, 1–19. [Google Scholar] [CrossRef]
  73. Bruschi, E.; Quaglini, V.; Calvi, P.M. A simplified design procedure to improve the seismic performance of RC framed buildings with hysteretic damped braces. In Proceedings of the New Metropolitan Perspectives 2022—5th International Symposium “Post COVID Dynamics: Green and Digital Transition, between Metropolitan and Return to Villages’ Perspectives”, Reggio Calabria, Italy, 25–27 May 2022; Volume 482, pp. 2173–2182, ISBN 978-3-031-06825-6. [Google Scholar]
  74. Priestley, M.J.N.; Calvi, G.M.; Kowalsky, M. Displacement-Based Seismic Design of Structures; IUSS Press: Pavia, Italy, 2007. [Google Scholar]
  75. Sullivan, T.; Maley, T.; Calvi, G.M. Seismic response of steel moment resisting frames designed using a Direct DBD procedure. In Proceedings of the 8th International Conference on Structural Dynamics, EURODYN, Leuven, Belgium, 4–6 July 2011. [Google Scholar]
  76. Barbagallo, F.; Bosco, M.; Marino, E.; Rossi, P. On the fibre modelling of beams in RC framed buildings with rigid diaphragm. Bull. Earthq. Eng. 2020, 18, 189–210. [Google Scholar] [CrossRef]
  77. Ponzo, F.C.; Di Cesare, A.; Telesca, A.; Pavese, A.; Furinghetti, M. Advanced modelling and risk analysis of RC buildings with sliding isolation systems designed by the Italian Seismic Code. Appl. Sci. 2021, 11, 1938. [Google Scholar] [CrossRef]
  78. Scozzese, F.; Gioiella, L.; Dall’Asta, A.; Ragni, L.; Tubaldi, E. Influence of viscous dampers ultimate capacity on the seismic reliability of building structures. Struct. Saf. 2021, 91, e102096. [Google Scholar] [CrossRef]
  79. Castaldo, P.; Tubaldi, E.; Selvi, F.; Gioiella, L. Seismic performance of an existing RC structure retrofitted with buckling restrained braces. J. Build Eng. 2021, 33, 101688. [Google Scholar] [CrossRef]
  80. Mazza, F.; Vulcano, A. Displacement-Based Design procedure of damped braces for the seismic retrofitting of RC framed buildings. Bull. Earthq. Eng. 2015, 13, 2121–2143. [Google Scholar] [CrossRef]
  81. Freddi, F.; Tubaldi, E.; Ragni, L.; Dall’Asta, A. Probabilistic performance assessment of low-ductility reinforced concrete frames retrofitted with dissipative braces. Earthq. Engng Struct. Dyn. 2013, 42, 993–1011. [Google Scholar] [CrossRef]
  82. SIMQKE (SIMulation of earthQuaKE ground motions). Available online: https://gelfi.unibs.it/software/simqke/simqke_gr.htm (accessed on 10 July 2022).
  83. Uang, C.M.; Bertero, V.V. Use of Energy as a Design Criterion in Earthquake-Resistant Design. Report No. UCB–EERC 88/18; University of California at Berkeley: Berkeley, CA, USA, 1988. [Google Scholar]
Figure 1. Sketch and nomenclature of the main elements of the PS-LED.
Figure 1. Sketch and nomenclature of the main elements of the PS-LED.
Materials 16 01933 g001
Figure 2. Effect of prestressing on the force of the PS-LED: yield force F0 vs. axial strain ε of the lead core calculated in the numerical analyses considering a shaft diameter (Ds) of either 20 mm or 32.5 mm (adapted from ref. [3]).
Figure 2. Effect of prestressing on the force of the PS-LED: yield force F0 vs. axial strain ε of the lead core calculated in the numerical analyses considering a shaft diameter (Ds) of either 20 mm or 32.5 mm (adapted from ref. [3]).
Materials 16 01933 g002
Figure 3. (a) The PS-LED prototype (highlighted with a dotted frame) on the testing machine, and (b) a typical force–displacement curve of the PS-LED.
Figure 3. (a) The PS-LED prototype (highlighted with a dotted frame) on the testing machine, and (b) a typical force–displacement curve of the PS-LED.
Materials 16 01933 g003
Figure 4. Force–displacement curve of the PS-LED prototype evaluated in the Ramp test.
Figure 4. Force–displacement curve of the PS-LED prototype evaluated in the Ramp test.
Materials 16 01933 g004
Figure 5. Changes in Keff and ξeff during the tests S1, S2, and S3.
Figure 5. Changes in Keff and ξeff during the tests S1, S2, and S3.
Materials 16 01933 g005
Figure 6. EPPV rheological model in OpenSees.
Figure 6. EPPV rheological model in OpenSees.
Materials 16 01933 g006
Figure 7. Matching of the numerical model with the experimental curve, and identified parameters of the EPPV model, adapted from [7].
Figure 7. Matching of the numerical model with the experimental curve, and identified parameters of the EPPV model, adapted from [7].
Materials 16 01933 g007
Figure 8. Elevation view and plan with the main dimensions of the RC case-study structure [9].
Figure 8. Elevation view and plan with the main dimensions of the RC case-study structure [9].
Materials 16 01933 g008
Figure 9. Reinforcement of (a) columns and (b) beams.
Figure 9. Reinforcement of (a) columns and (b) beams.
Materials 16 01933 g009
Figure 10. Elevation view and plan with the main dimensions of the steel case-study structure [59,60].
Figure 10. Elevation view and plan with the main dimensions of the steel case-study structure [59,60].
Materials 16 01933 g010
Figure 11. Capacity curves in the X-direction and limit values of displacements for the two case-study structures: (a) RC building, and (b) steel MRF building.
Figure 11. Capacity curves in the X-direction and limit values of displacements for the two case-study structures: (a) RC building, and (b) steel MRF building.
Materials 16 01933 g011
Figure 12. Plan layout of the Chevron braces equipped with the PS-LED: (a) RC structure, and (b) steel MRF.
Figure 12. Plan layout of the Chevron braces equipped with the PS-LED: (a) RC structure, and (b) steel MRF.
Materials 16 01933 g012
Figure 13. Elevation layout of Chevron braces equipped with the PS-LED in the RC case-study structure.
Figure 13. Elevation layout of Chevron braces equipped with the PS-LED in the RC case-study structure.
Materials 16 01933 g013
Figure 14. Force–deflection diagram of a single brace equipped with the PS-LED.
Figure 14. Force–deflection diagram of a single brace equipped with the PS-LED.
Materials 16 01933 g014
Figure 15. Maximum inter-story drift ratio Δ in the X-direction obtained by NLDAs: (a) RC structure, and (b) steel MRF.
Figure 15. Maximum inter-story drift ratio Δ in the X-direction obtained by NLDAs: (a) RC structure, and (b) steel MRF.
Materials 16 01933 g015
Figure 16. Peak floor acceleration PFA in the X-direction obtained by NLDAs: (a) RC structure, and (b) steel MRF.
Figure 16. Peak floor acceleration PFA in the X-direction obtained by NLDAs: (a) RC structure, and (b) steel MRF.
Materials 16 01933 g016
Figure 17. Acceleration and displacement spectra for the RC frame in the as-built and retrofitted configurations, showing the combined effect of structural stiffening introduced by the brace and damping of the PS-LED.
Figure 17. Acceleration and displacement spectra for the RC frame in the as-built and retrofitted configurations, showing the combined effect of structural stiffening introduced by the brace and damping of the PS-LED.
Materials 16 01933 g017
Figure 18. Maximum shear force V in the X-direction: (a) RC structure, and (b) steel MRF.
Figure 18. Maximum shear force V in the X-direction: (a) RC structure, and (b) steel MRF.
Materials 16 01933 g018
Figure 19. Maximum shear forces in the most stressed column (position C11 in Figure 12a) of the RC structure.
Figure 19. Maximum shear forces in the most stressed column (position C11 in Figure 12a) of the RC structure.
Materials 16 01933 g019
Figure 20. Check of column C11 (Figure 12a) at the ground floor of the RC structure in the M–N interaction diagram.
Figure 20. Check of column C11 (Figure 12a) at the ground floor of the RC structure in the M–N interaction diagram.
Materials 16 01933 g020
Figure 21. Buckling check of column C14 (Figure 12b) of the steel MRF.
Figure 21. Buckling check of column C14 (Figure 12b) of the steel MRF.
Materials 16 01933 g021
Figure 22. Comparison of energy time histories of the buildings and the total energy dissipated by the PS-LED dampers calculated for the most demanding input accelerogram.
Figure 22. Comparison of energy time histories of the buildings and the total energy dissipated by the PS-LED dampers calculated for the most demanding input accelerogram.
Materials 16 01933 g022
Figure 23. Force–displacement cycles of the PS-LED dampers at each floor of the steel MRF calculated for the most demanding input accelerogram.
Figure 23. Force–displacement cycles of the PS-LED dampers at each floor of the steel MRF calculated for the most demanding input accelerogram.
Materials 16 01933 g023
Table 1. Testing protocol according to the EN 15129 [53].
Table 1. Testing protocol according to the EN 15129 [53].
Test d [mm]f [Hz]No. of Cycles [-]
CyclicC150.55
C2100.55
C3200.510
RampR26.40.0011
DynamicD1200.255
D2200.505
D3200.755
S1200.510
SurvivabilityS2200.510
S3200.510
d: cycle amplitude; f: test frequency.
Table 2. Stability requirements [53] and results of the tests on the PS-LED prototype.
Table 2. Stability requirements [53] and results of the tests on the PS-LED prototype.
RequirementC1
d = 5 mm
C2
d = 10 mm
C3
d = 20 mm
K eff , i K eff , 3 K eff , 3     0 . 10 +1.8%−5.2%−9.3%
ξ eff , i   ξ eff 3 ξ eff , 3     0 . 10 −1.3%−3.6%−2.2%
Keff,i and ξeff,i are the effective stiffness and the equivalent damping ratio evaluated at the i-th cycle (i ≥ 2), respectively. Keff,3 and ξeff,3 are the effective stiffness and the equivalent damping ratio evaluated at the third cycle, respectively.
Table 3. Effect of velocity on the properties of the PS-LED prototype.
Table 3. Effect of velocity on the properties of the PS-LED prototype.
RequirementD1
f = 0.25 Hz
D2
f = 0.50 Hz
D3
f = 0.75 Hz
K eff , 3 [kN/mm]21.822.323.2
ξ eff , 3 [%]53.655.355.1
Table 4. Elastic stiffness K 1 and yield force F 0 of the PS-LED dampers installed at each story of the RC structure.
Table 4. Elastic stiffness K 1 and yield force F 0 of the PS-LED dampers installed at each story of the RC structure.
Story X-Direction Z-Direction
K1
[kN/mm]
F0
[kN]
K1
[kN/mm]
F0
[kN]
4th499.644.0499.244.5
3rd529.696.0533.697.0
2nd535.7133.9540.9135.2
1st644.0152.4656.8153.7
Table 5. Elastic stiffness K 1 and yield force F 0 of the PS-LED dampers installed at each story of the steel MRF.
Table 5. Elastic stiffness K 1 and yield force F 0 of the PS-LED dampers installed at each story of the steel MRF.
Story X-Direction
K1
[kN/mm]
F0
[kN]
4th358.6207.9
3rd378.0400.4
2nd418.4531.6
1st602.3588.8
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Bruschi, E.; Zoccolini, L.; Cattaneo, S.; Quaglini, V. Experimental Characterization, Modeling, and Numerical Evaluation of a Novel Friction Damper for the Seismic Upgrade of Existing Buildings. Materials 2023, 16, 1933. https://doi.org/10.3390/ma16051933

AMA Style

Bruschi E, Zoccolini L, Cattaneo S, Quaglini V. Experimental Characterization, Modeling, and Numerical Evaluation of a Novel Friction Damper for the Seismic Upgrade of Existing Buildings. Materials. 2023; 16(5):1933. https://doi.org/10.3390/ma16051933

Chicago/Turabian Style

Bruschi, Eleonora, Luca Zoccolini, Sara Cattaneo, and Virginio Quaglini. 2023. "Experimental Characterization, Modeling, and Numerical Evaluation of a Novel Friction Damper for the Seismic Upgrade of Existing Buildings" Materials 16, no. 5: 1933. https://doi.org/10.3390/ma16051933

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop